DirecDoor Installation Guide

55

Available Resistance Combinations

OnGuard System Administration - EOL Resistor Tables Form

The values created in OnGuard as shown above can be used as an example of how to configure a 1k-
1k end of line circuit. 

Tamper conditions are generated when the input values fall below 750 ohms, when they are 
between 1250 ohms and 1550 ohms, or when they exceed the 2500 ohms resistance. 

Any values within the Normal low range represent an 

Alarm Restored

 event. 

An 

Alarm Active

 condition is reported when the input resistance falls in the 

Normal high

 range. 

Notice that both the 

Alarm Restored

 and 

Alarm Active

 states need to be wide enough to accommodate 

important factors, such as the cable length resistance (approximately 10 

Ω

 /1000 feet) and the 

granularity of the controller’s A2D (analog to digital) device.

Resistor Table 3

 on page 

55

 summarizes the expected events under this configuration.

Resistor Table 3

Table 

Resistances Detected by PXNplus

 on page 

56

 summarizes the resistance values detected by the 

PXNPlus controller.

Summary of Contents for DirecDoor

Page 1: ...7 4 DirecDoor Installation Guide...

Page 2: ...D Technologies Inc ALL RIGHTS RESERVED Active Directory Microsoft SQL Server Windows and Windows Server are either registered trademarks or trademarks of Microsoft Corporation in the United States and...

Page 3: ...ROL INCLUDING BUT NOT LIMITED TO INTERNET CELLULAR AND LANDLINE CONNECTIVITY MOBILE DEVICE AND RELATED OPERATING SYSTEM COMPATABILITY OR PROPER INSTALLATION CONFIGURATION AND MAINTENANCE OF AUTHORIZED...

Page 4: ......

Page 5: ...Prevention Procedures 17 Signal Transmission 17 Cable Routing 17 Cable Length 17 Mounting 17 Mounting and Handling Guidelines 17 Mounting Instructions 18 Determining Power Requirements 20 CHAPTER 3 P...

Page 6: ...ng the DIP Switches 37 Setting the Jumpers 39 Wiring the Readers 39 Wiring the Digital Inputs DIs 43 Wiring the Door Strikes 44 Wiring the Fire Alarm Control Panel 46 CHAPTER 6 DDIO Interface 47 Direc...

Page 7: ...ler Parameters Menu Other Parameters Form 71 Disable Enable the Integrated Configuration Tool ICT 72 Upgrading the Controller Firmware 72 Configuration Checklist for the Integrated Configuration Tool...

Page 8: ...Table of Contents 8 DirecDoor Installation Guide...

Page 9: ...buted processing for the interface of access control readers keypads alarm inputs and outputs back to a host system computer This distributed processing allows each DirecDoor controller to operate ind...

Page 10: ...fications For UL compliant installations refer to UL Compliance on page 80 Enclosure Specifications Physical dimensions 10 15 inches high x 9 15 inches wide x 3 04 inches deep 258 mm high x 232 mm wid...

Page 11: ...y and alarm cable commercial applications shielded plenum rated Controller to DIs or DOs Use any cable with the desired number of individually shielded pairs Devices Readers Number supported maximum o...

Page 12: ...90 Model T720 reader 12 75 0 90 Model T725 reader 12 110 1 32 Securitron M62 Magnalock strikea 12 240 2 88 Securitron M62 Magnalock strikea a When using magnetic strikes with auto voltage select addit...

Page 13: ...a Type 3 SIMMb Operating system uClinux 2 6 uClinux 2 6 Processor Xilinx MicroBlaze Xilinx MicroBlaze RAM 32 MB 64 MB Flash memory 32 MB 32 MB Host Application and Capacities All currently supported v...

Page 14: ...Introduction 14 DirecDoor Installation Guide...

Page 15: ...ply power to any component until the installation is complete Damage to components may occur if power is incorrectly applied 1 Determine the cable clamps needed and obtain them before starting the ins...

Page 16: ...be produced when walking across a carpet and touching a board for example Before handling any board make sure you dissipate your body s charge by touching ground This discharges any static electricit...

Page 17: ...ve machinery such as air conditioners elevators escalators large blowers and machine tools Electromagnetic equipment such as degaussers magnetic chucks etc Control equipment relays for machinery and o...

Page 18: ...direct sunlight To avoid mechanical damage do not drop or stack boards Do not subject printed circuit boards to electrostatic discharge Mounting Instructions Mount the controller cabinet using the fol...

Page 19: ...DirecDoor Installation Guide 19 Mounting DirecDoor Mounting Template...

Page 20: ...Guide DirecDoor Controller and Components in Standard Enclosure Determining Power Requirements Use the DirecDoor Wattage Calculator worksheet below to help plan your installation An Excel XLS version...

Page 21: ...If this is a UL Listed installation refer to Regulatory Information on page 77 Note The DDSDC does not support the optional dial up modem or DirecDoor I O expansion board as shown below in the wattag...

Page 22: ...Installation Planning and Mounting 22 DirecDoor Installation Guide...

Page 23: ...ng power Network Connector J10 as Power over Ethernet PoE Auxiliary Power Connector J8 with 24 VDC supply and battery backup J8 Power Input Port Connector J8 Pin Signal Name 1 24 VDC Auxiliary Power I...

Page 24: ...upplied ferrite to the network cable as shown in figure Installing Ferrite on page 78 3 Connect the network cable to J10 on the DirecDoor board Note By Ethernet standards the maximum cable length is l...

Page 25: ...WARNING Do not ground both cable ends Note If the polarity is reversed the fuse blows to prevent damage If the fuse blows it automatically resets within approximately 5 seconds 3 Install the cabinet g...

Page 26: ...n has not been evaluated by UL at this time Connect AC power fail input from a battery backup unit to connector J8 between pin 2 Gnd or pin 4 Gnd and pin 3 AC fail The battery backup unit must supply...

Page 27: ...ng network protocols DHCP and UDP Provides nonvolatile storage referred to as persistent mode of operation This means a faster reset recovery and allows for host less operation Utilizes a 32 bit platf...

Page 28: ...ecDoor Board 28 DirecDoor Installation Guide DirecDoor Board Layout Note The DDSDC does not have the following hardware components as shown in the figure above Connectors J4 J5 J7 and J11 and Switch S...

Page 29: ...o five 5 seconds for D19 to turn ON Once D19 is ON release SW4 D19 turns OFF once the Integrated Configuration Tool has been manually enabled SW5 Hardware Reset Reboots the DirecDoor board The switch...

Page 30: ...O Notes The DDSDC does not have Connector J5 and does not support the DDIO Not evaluated by UL at this time J6 Connector J6 is a pluggable screw terminal block For connector J6 pinouts refer to table...

Page 31: ...or J10 is an RJ45 Standard Cat 5 jack which controls the RJ45 network connection J11 Not Used Connector J11 is an RJ11 standard telephone jack Note The DDSDC does not have Connector J11 J9 Console Por...

Page 32: ...oller decoded a badge read and determined that it was a valid badge Waiting for database D17 Flashes the controller is waiting to receive database from host Restore defaults requested D17 and D21 On i...

Page 33: ...mode Controller offline ON Address received ON Badge read ON Waiting for panel configuration Flashesa a For OnGuard systems D17 blinks twice followed by a one second delay before repeating Restore def...

Page 34: ...lash write Flashes Manual ICT Enable ON Watch dog failure mode ON OFF Input LEDs on the DirecDoor Board LED Number Name Description D24 FACP Fire Alarm Connection Point ON Open OFF Closed D25 Door Con...

Page 35: ...sts for approximately 40 to 45 seconds after which the system will auto restart D27 Door Contact 2 Indicates physical input state ON Closed OFF Open Flashing Fault D28 Door REX 2 Indicates physical in...

Page 36: ...following products use this port Integrated Configuration Tool DirecDoor M5PXNplus M2000PXNplus M3000PXNplus Configuring Upstream Communications with the Host 1 Verify that you have a working network...

Page 37: ...o only one type of reader technology Wiegand F 2F or Supervised F 2F The reader interface has built in pull up resistors to accommodate cable lengths over 500 feet 152 40 m External pull up resistors...

Page 38: ...vised F 2F default ON ON Magstripe Strobed ON ON Magstripe F 2F ON ON ON Wiegand format a ON a Use the OnGuard application to configure the specific Wiegand card formats OFF Supervised DI REX SW1 7 Su...

Page 39: ...e to the grounding nuts provided outside the controller enclosure Refer to figure Wiring to Wiegand Readers Door Contacts and Exit Request on page 42 4 Place the appropriate wires to the appropriate s...

Page 40: ...t DI on Connector J2 Refer to figure Wiring to Wiegand Readers Door Contacts and Exit Request on page 42 J1 J3 Connecting T 5xx Series Reader J1 J3 Pin Signal Name Reader Pigtail Colors 1 12 VDC Red 2...

Page 41: ...lay Power on page 45 and figure Wiring Door Strikes External Relay Power on page 45 Dressing the Reader DO DI Wiring Inside the DirecDoor Enclosure 7 Door Strike Relay Common Com Brown 8 Door Strike R...

Page 42: ...ader Interface 42 DirecDoor Installation Guide Wiring to Wiegand Readers Door Contacts and Exit Request Note The DDSDC only supports one door strike DO relay one alarm DI and one exit DI on Connector...

Page 43: ...ital Inputs DIs Note The DDSDC only supports one alarm DI and one exit DI on Connector J2 Each reader DI port J2 J4 has two digital inputs which are used for door status devices door contacts and exit...

Page 44: ...ation of the resistors Refer to table Supervised DI REX on page 38 for the appropriate switch settings 6 Wire the supervised door DI between pin 1 Door DI and pin 2 Door DI Return 7 Wire the supervise...

Page 45: ...recDoor Installation Guide 45 Wiring the Door Strikes Note Protection diode or MOV required at all electronic door locks Wiring Door Strikes Internal Relay Power Wiring Door Strikes External Relay Pow...

Page 46: ...llation Guide Wiring the Fire Alarm Control Panel If a Fire Alarm Control Panel FACP is not used the jumper on J6 FACP Input must remain in place for correct operation J6 FACP Input Normally Closed Pi...

Page 47: ...C each Wiring cable size 22 AWG 0 33 mm2 Use 22 AWG shielded cable Recommended Alpha Xtra Guard1 foil shield cable non plenum rated and Belden series security and alarm cable commercial applications s...

Page 48: ...I O Expansion Board the DirecDoor RS485 communications must be enabled and the DIP switches set as described in the tables below Note The bus address is always 4 DDIO RS485 SW2 DIP Switch Settings Mod...

Page 49: ...OFF OFF RS485 2 wire N A N A ON ON DDIO Input Termination Resistors and Supervised Configuration SW5 DIP Switch Settings Mode SW 5 1 SW 5 2 SW 5 3 SW 5 4 0 5K alarm 1K safe 2K alarm OFF OFF OFF ON 1K...

Page 50: ...nting the DDIO Board in the DirecDoor Enclosure on page 51 2 Mount the DirecDoor I O Expansion Board to the DirecDoor enclosure using fasteners as shown in Figure Mounting the DDIO Board in the DirecD...

Page 51: ...or controller 1 Install the four standoffs into the back of the DirecDoor I O Expansion Board s shown in Figure Mounting the DDIO Board in the DirecDoor Enclosure on page 51 2 Mount the DirecDoor I O...

Page 52: ...ing To wire power and RS485 communication to the DirecDoor I O Expansion Board refer to Figure Power and RS485 Wiring on page 52 Power and RS485 Wiring Input and Output Device Wiring For input device...

Page 53: ...ance values The purpose of this feature is to provide an additional level of flexibility to the end user and depart from the conventional 1k 1k termination The tables in this section illustrate the ex...

Page 54: ...stor and X is left unchanged Circuit 2 Resistor Table 2 Note The resistance values used to build the tables above do not account for the additional resistance of the cable connected to the DDIO board...

Page 55: ...hin the Normal low range represent an Alarm Restored event An Alarm Active condition is reported when the input resistance falls in the Normal high range Notice that both the Alarm Restored and Alarm...

Page 56: ...DDIO Interface 56 DirecDoor Installation Guide Resistances Detected by PXNplus...

Page 57: ...shielded stranded wire is recommended for the DO interface Wiring Digital Outputs DOs Digital DOs are obtained by using unassigned reader outputs When used as DOs these outputs require pull up resisto...

Page 58: ...DO Interface 58 DirecDoor Installation Guide Wiring Output Device to DO Interface...

Page 59: ...of OnGuard that are licensed for ACU feature support The DirecDoor controllers must have a compatible firmware version R020 or later The DirecDoor CPU uses a Type 3 SIMM flashed with R020 or later fi...

Page 60: ...cDoor Dual NIC DirecDoor Dual NIC Primary and Secondary Network Cable Connections Configuration To configure the DirecDoor Dual NIC using the ICT refer to Controller Parameters Menu Secondary Network...

Page 61: ...ge should be 24 VDC nominal d Use a voltmeter to measure the input voltage across J8 at pin 1 and pin 2 Verify proper polarity and voltage Pin 1 Power pin 2 or pin 4 Ground Reverse the wiring if neces...

Page 62: ...DirecDoor Installation Guide Result A measurement of 100 ohms indicates a short circuit Correct this condition before powering up 4 Reconnect all disconnected plugs DirecDoor powers up and begins its...

Page 63: ...tion reports Software and Hardware Requirements A supported Internet browser Refer to the OnGuard Release Notes for supported browsers and versions One of the following setups Cat 5 cable with network...

Page 64: ...he computer you are using to access the Integrated Configuration Tool If yes disable the firewall in order to use the Integrated Configuration Tool Is your network using a proxy If yes disable the pro...

Page 65: ...r You will need to reset your computer back to these numbers once the controller configuration is complete 6 Enter the IP address 192 168 6 5 or a similar valid IP address 192 168 6 x where x is any n...

Page 66: ...before switching to another form This action saves your latest changes to a temporary file After completing all the forms click Reset Controller for the changes to take effect Changes will be saved to...

Page 67: ...orts which are provided for checking and monitoring the controller These reports are used by technical support staff to troubleshoot controller issues Information Form Selection Items 1 Click the Cont...

Page 68: ...dware related information such as boot and board version FPGA version SIMM type available hardware devices physical memory size SDRAM BRAM FLASH and FLASH memory type OS Info Displays information rela...

Page 69: ...menu and select the Primary Network form 2 Make sure the Enable IPV4 check box is selected 3 In the Controller Information section set the controller IP addressing Static or dynamic DHCP Refer to the...

Page 70: ...in the MAC address field Note Give the MAC address to your Network Administrator so that it can be added to the DNS database 3 Click Save 4 If this completes your controller configuration click Reset...

Page 71: ...set the static IP address or select DHCP refer to the instructions for the Controller Parameters Menu Primary Network Form on page 68 5 Click Save 6 If this completes your controller configuration cli...

Page 72: ...ontroller Parameters menu select Other Parameters 3 Check the Disable Integrated Configuration Tool box and click OK 4 To permanently disable the ICT click Save The ICT web page closes and the ICT is...

Page 73: ...roller in the hardware view and select Download Firmware Alarm Monitoring System Status Window 3 When the following message appears click Yes to confirm the download Firmware Download Confirmation 4 W...

Page 74: ...lect the following information Configuring the Host Application Configuring the DirecDoor Controller in the Host Application Set up this controller as you would any other NGP controller by using the N...

Page 75: ...NIC in the Host Application 1 In the OnGuard System Administration application Access Panels folder use the NGP CASI Form to configure your controller 2 On the Primary Connection tab select LAN enter...

Page 76: ...Controller Firmware Tools 76 DirecDoor Installation Guide...

Page 77: ...nected to the DirecDoor must be shielded with shield terminated as shown in figure Typical Installation Using Shielded Cable Drain Wire on page 78 Use 8 32 SEMS screws provided The DirecDoor enclosure...

Page 78: ...Regulatory Information 78 DirecDoor Installation Guide Typical Installation Using Shielded Cable Drain Wire Installing Ferrite...

Page 79: ...DirecDoor Installation Guide 79 CE Regulatory Notice CE Regulatory Notice...

Page 80: ...be protected with a Secondary Protector for Communication Circuits Listed under UL 497A The monitoring equipment must be installed in a temperature controlled environment with 24 hours of standby pow...

Page 81: ...tional Electrical Code The DirecDoor must be used with listed card readers The exit request input circuit and initiating device must be contained within the secured area The exit device circuit must b...

Page 82: ...ustrial supervision A clearly marked redundant system with the same configuration as the primary machine should be available as a backup In order for this product to be UL compliant the firmware level...

Page 83: ...on page 26 If the LED is not on do the following 1 Use a voltmeter to check the power supply output It should read 24 VDC nominal If there is no output make sure the power supply is not on a switched...

Page 84: ...but the door strike does not operate Resolution 1 Check the wiring from the door strike to the reader interface In the chapter of the appropriate reader interface refer to the section that covers wir...

Page 85: ...nect Resolution 1 Verify your network settings host IP address OnGuard systems controller IP address and controller address OnGuard systems network mask gateway IP DHCP 2 Check the connectivity using...

Page 86: ...on procedures Refer to Electrostatic Discharge ESD Precaution on page 16 2 Locate the clips on the right and left sides of the UCSIMMPlus board Press both clips out 3 Pull out the UCSIMMPlus board 4 T...

Page 87: ...iew 47 resistance combinations 53 specifications 47 wiring input device 52 output device 52 power 52 RS485 52 DDSDC hardware limitations 9 21 24 27 28 29 30 31 33 37 40 42 43 44 47 59 61 66 70 80 Devi...

Page 88: ...Parameters form 71 P Parameters form 66 Power input port 23 Power LED 23 Power over Ethernet 24 Power problems 83 Power requirements 20 Primary Network form 68 R Radio interference 16 Reader interfac...

Page 89: ...DirecDoor Installation Guide 89 Index...

Page 90: ...UTC Fire Security Americas Corporation Inc 1212 Pittsford Victor Road Pittsford New York 14534 USA Tel 866 788 5095 Fax 585 248 9185 www lenel com docfeedback lenel com...

Reviews: