DirecDoor Board
32
DirecDoor Installation Guide
W5
LED Indicators on the DirecDoor Board
Normal Operation Mode is the mode that the controller is in after application updates have been
made. During normal operation, the Watchdog LED (D19) flashes once per second.
Note:
After updates are made to the controller, or power is cycled to the controller, and the
Watchdog LED (D19) starts flashing, wait at least four (4) minutes before attempting
any button commands. During this period, the panel software is initializing and the user
buttons are not monitored. At the end of this period, the Watchdog LED turns off for one
second, and then flashes once per second to indicate that the controller is in Normal
Operation Mode. At this time, the user buttons are monitored.
During Normal Operation Mode, the following additional states can occur:
•
Controller offline (D14 On)
: the controller has lost communication with the host.
•
Address received (D15 On)
: the controller receives a message from the host.
•
Badge read OK (D16 On)
: the controller decoded a badge read and determined that it was a
valid badge.
•
Waiting for database (D17 Flashes)
: the controller is waiting to receive database from
host.
•
Restore defaults requested (D17 and D21 On)
: indicates SW7 (Restore defaults switch)
was pressed which requests that the defaults be restored.
•
Shutdown requested (D17 through D21 On)
: Request a safe halt of all processes running
in the panel. Required for safe power down.
•
eFlash image save (D20 and D21 alternates On)
: indicates that the newly loaded image
from the eFlash transfer is being saved into the flash. This is an activity indicator only.
•
Flash write (D19 Flashes)
: indicates that the controller is storing database records into the
flash file system. This is an activity indicator only.
•
Manual ICT Enable (D19 On)
: indicates SW4 (Boot mode switch) was pressed which
manually enables the Integrated Configuration Tool.
Refer to table
DirecDoor Board LED Normal State Transitions (D14 through D18)
and
DirecDoor Board LED Normal State Transitions (D19 through D21, D51, D52)
normal LED state transitions.
Refer to table
DirecDoor Board LED Fault Conditions
for error conditions.
W5 - Tamper
Function
W5 Pins
Tamper Input
1 and 2
Summary of Contents for DirecDoor
Page 1: ...7 4 DirecDoor Installation Guide...
Page 4: ......
Page 8: ...Table of Contents 8 DirecDoor Installation Guide...
Page 14: ...Introduction 14 DirecDoor Installation Guide...
Page 19: ...DirecDoor Installation Guide 19 Mounting DirecDoor Mounting Template...
Page 22: ...Installation Planning and Mounting 22 DirecDoor Installation Guide...
Page 56: ...DDIO Interface 56 DirecDoor Installation Guide Resistances Detected by PXNplus...
Page 58: ...DO Interface 58 DirecDoor Installation Guide Wiring Output Device to DO Interface...
Page 76: ...Controller Firmware Tools 76 DirecDoor Installation Guide...
Page 79: ...DirecDoor Installation Guide 79 CE Regulatory Notice CE Regulatory Notice...