Installation and start-up of KEOR HPE UPS 60÷80 kVA
Installation et démarrage de l’ASI KEOR HPE 60÷80 kVA
Installazione e avviamento KEOR HPE UPS 60÷80 kVA
34
OMW07096 REV. E
Details of the electrical connections
Power (kVA)
60
80
Input fuses [A]
Rectifier 125
160
Bypass 100
125
Phase conductor cross sect. [mm
2
]
Rectifier
4x (1x50)
4x (1x70)
Bypass
4x (1x35)
4x (1x50)
Output
4x (1x35)
4x (1x50)
Battery
3x (1x35)
3x (1x70)
Neutral conductor sizing
Linear load
Same as the phase conductor
NON-linear load
1,5
x phase conductor cross section
Earth conductor cross sect. [mm
2
]
25 35
Power connections
Type Aluminium
bars
Conductor max. cross section [mm
2
] 50
95
Max. number of conductors
2
Fixing bolt dimensions
M10
Tightening torque [Nm]
42 ÷ 53
The sections given in the table above are indicative only. The cables have been designed according to
the standard CEI-UNEL35024/1, using the following data:
70° C rated PVC copper cables
ambient temperature equal to 40° C
maximum length of the cables equal to 30 m (voltage drop < 0,5%)
cables laid in cavities of structures or solid bottom cable trays
The given cross sections do not take into account the overload currents allowed by each line, which are
detailed in the product Technical Specification.
The UPS manufacturer is not responsible for the correct sizing of the device supply and output lines for
which the plant conditions and operating temperatures, which are specific of each electrical installation,
must be taken into account.
Rated current (at full load and battery recharging)
Power (kVA)
60
80
Rectifier input [A]
(1)
129
170
Bypass input / Output [A]
(2)
87 115
Battery [A]
100
133
(1)
Values referred to 400Vac -15%
(2)
Values referred to 400Vac , for overload refer to technical specification