![LEGRAND 311087 Operating Manual Download Page 57](http://html.mh-extra.com/html/legrand/311087/311087_operating-manual_1872151057.webp)
Installation and start-up of KEOR HPE UPS 60÷80 kVA
Installation et démarrage de l’ASI KEOR HPE 60÷80 kVA
Installazione e avviamento KEOR HPE UPS 60÷80 kVA
32
OMW07096 REV. E
4 ELECTRICAL CONNECTION
The electrical connection is part of the work which is normally provided by the company that carries out
the product installation. For this reason, the UPS manufacturer shall not be held responsible for any
damages due to wrong connections.
Use qualified personnel only
All the operations related to the electric connection must be carried out by qualified and
trained personnel.
Work in compliance with the local standards
The installation of the KEOR HPE UPS 60÷80 kVA must be carried out in compliance with
national and local regulations.
Connection of ground cable
The grounding of the UPS via the relevant terminal is mandatory. It is strongly recommended
to connect the ground terminal as first terminal.
The electrical connection is part of the work which is normally provided by the company that carries out
the electrical installation and not by the UPS manufacturer. For this reason, the following
recommendations are only an indication, as the UPS manufacturer is not responsible for the electrical
installation. In any case we recommend to carry out the installation and the electrical input and output
connections in compliance with the local standards.
Cables must be selected bearing in mind technical, financial and safety aspects. The selection and the
sizing of cables from a technical viewpoint depend on the voltage, on the current absorbed by the UPS,
on the bypass line and on the batteries, on the ambient temperature and on the voltage drop. Finally, the
kind of cable laying must be taken into particular consideration.
For more explanations regarding the selection and the sizing of cables, please refer to the relevant IEC
standards, in particular to IEC 64-8 standard.
“Short-circuit currents” (very high currents with a short duration) and “overload currents” (relatively high
currents with a long duration) are among the main causes of cable damage. The protection systems
normally used to protect the cables are: thermal magnetic circuit breakers or fuses. Protection circuit
breakers must be selected according to the maximum short-circuit current (max Isc) that is needed to
determine the breaking power of automatic circuit breakers, and to the minimum current (min Isc) that is
needed to determine the maximum length of the line protected. The protection against short-circuit must
operate on the line before any thermal and electrothermal effects of the overcurrents may damage the
cable and relevant connections.
During the electrical installation take particular care to respect the phase rotation.
The terminal boards are placed on the front of the UPS. To access the terminals remove the front panel,
removing the fixing bolts.