Installation and start-up of KEOR HPE UPS 60÷80 kVA
Installation et démarrage de l’ASI KEOR HPE 60÷80 kVA
Installazione e avviamento KEOR HPE UPS 60÷80 kVA
26
OMW07096 REV. E
3.3.1 Base plan, static load and weights
GLAND PLATE
118
49
4
24
24
58
2
Ø
8
387
387
57
Picture 3 – Base plan
The supporting base of the UPS must be designed to carry the UPS weight and to ensure its steady and
safe support.
Its carrying capacity must be adequate to the static loads indicated in the table below.
Power (kVA)
60
80
Weight w/o batteries (kg)
225
250
Static load w/o batteries (kg/m
2
) 430
480
Weight with batteries (kg)
780
800
Static load with batteries (kg/m
2
)
1480 1530