40
Also we can use addresses 127 to get the UPS status. A decimal value will be received from address 127. If that value is
converted to binary number, the UPS status can be read.
bit 0
UPS operates on Online Mode
bit 1
UPS operates on Bypass Mode
bit 2
UPS operates on Battery Mode
bit 3
Output voltage is out of limits
bit 4
Output overload
bit 5
Inverter temperature is high
bit 6
Rectifier temperature is high
bit 7
Ambient temperature is high
bit 8
Bypass is not synchronized
bit 9
Maintenance Bypass Breaker is “ON”
bit 10
UPS operates on Green Mode
bit 11
Battery Failure
bit 12
ESD interface is activated
bit 13
DC Bus voltage is out of limits
bit 14
General Alarm
Example:
Let's receive 28673 (DEC) from address 127. If that value is converted to binary number, 111000000000001
will be obtained. Then the following status can be read from that number:
Online Mode
ESD interface is activated
DC Bus voltage is out of limits
General Alarm
Summary of Contents for 30 KVA
Page 1: ...KEOR T 10 60 KVA INSTALLATION MANUAL ...
Page 4: ...IV Installation Operating Manuals Battery Fast Fuses ...
Page 30: ...25 KEOR T 10 30kVA 1x60pcs 7 9Ah BATTERY WIRING DIAGRAM Figure 5 3 1 4 1 ...
Page 31: ...26 KEOR T 10 30kVA 2x60pcs 7 9Ah BATTERY WIRING DIAGRAM Figure 5 3 1 4 2 ...
Page 32: ...27 KEOR T 40 60kVA 2x60pcs 7 9Ah BATTERY WIRING DIAGRAM Figure 5 3 1 4 3 ...
Page 33: ...28 KEOR T 40 60kVA 3x60pcs 7 9Ah BATTERY WIRING DIAGRAM Figure 5 3 1 4 4 ...
Page 46: ...41 Appendix 3 Description of UPS and Block Diagram SEPARATED RECTIFIER AND BYPASS INPUTS ...