8.3. Emergency Switching Device and Generator Connections
Voltage to be applied to the digital inputs is 5VDC. Maximum current drawn by each input is 1mA. 5VDC supply
provided on the communication interface board can be used to supply both digital inputs.
UPS output can be switched off immediately by Remote Emergency Switching Device interface (ESD) connection if
desired. A remote latched switch can be used as described in above figure.
Input
Function
UPS OFF
If the UPS OFF input is set high by applying 5VDC voltage on the related terminals, UPS stops
generating the output voltage and stops feeding the load. When the voltage on the digital
input is removed, you have to restart UPS.
The factory default setting of ESD contact is
“Normally open”.
GEN ON
If the GEN ON input is set high by applying 5VDC voltage on the related terminals, UPS
transfers to Generator Mode, bypass and battery charging is disabled. Generator icon appears
on Energy Flow Diagram screen.
The factory default setting of Generator contact is “Normally
open”.
Tablo.9
Pay attention to the polarity of the voltages applied to the digital input terminals.
Figure.8.3-1
Summary of Contents for 30 KVA
Page 1: ...KEOR T 10 60 KVA INSTALLATION MANUAL ...
Page 4: ...IV Installation Operating Manuals Battery Fast Fuses ...
Page 30: ...25 KEOR T 10 30kVA 1x60pcs 7 9Ah BATTERY WIRING DIAGRAM Figure 5 3 1 4 1 ...
Page 31: ...26 KEOR T 10 30kVA 2x60pcs 7 9Ah BATTERY WIRING DIAGRAM Figure 5 3 1 4 2 ...
Page 32: ...27 KEOR T 40 60kVA 2x60pcs 7 9Ah BATTERY WIRING DIAGRAM Figure 5 3 1 4 3 ...
Page 33: ...28 KEOR T 40 60kVA 3x60pcs 7 9Ah BATTERY WIRING DIAGRAM Figure 5 3 1 4 4 ...
Page 46: ...41 Appendix 3 Description of UPS and Block Diagram SEPARATED RECTIFIER AND BYPASS INPUTS ...