![LEGRAND 30 KVA Installation Manual Download Page 18](http://html.mh-extra.com/html/legrand/30-kva/30-kva_installation-manual_1872147018.webp)
13
Remove the side parts which prevent the transpallet to damage the UPS.
Unload the UPS from the pallet.
5.3. Installation Procedures and Instructions
It is recommended to store the original UPS packaging for future needs.
The equipment may only be installed and commissioned by authorized LEGRAND UPS Technical
Service Staff or authorized LEGRAND distributor Technical Service Staff.
When the UPS is brought from a cold place to a warmer place, humidity of the air may condensate in
it. In this case, wait minimum for 2 (two) hours before powering the UPS.
KEOR T must be protected from voltage surge with devices that are suited to the installation; the
mains voltage surge must be limited to 2kV. These protective devices must be sized to take into
account all the installation parameters (geographical position whether or not there is a lightning rod,
whether or not there are other suppressors in the electrical installation, etc )
Do not connect the output neutral to the protective ground or protective bounding (except the TNC
Option). Keor T does not modify the neutral arrangements of the system; the use of an isolation
transformer is required should it be necessary to modify the neutral arrangements downstream Keor T.
Power cables and communication cables shall be installed on trays according to the standards of the
country.
Figure.5.2-4
Summary of Contents for 30 KVA
Page 1: ...KEOR T 10 60 KVA INSTALLATION MANUAL ...
Page 4: ...IV Installation Operating Manuals Battery Fast Fuses ...
Page 30: ...25 KEOR T 10 30kVA 1x60pcs 7 9Ah BATTERY WIRING DIAGRAM Figure 5 3 1 4 1 ...
Page 31: ...26 KEOR T 10 30kVA 2x60pcs 7 9Ah BATTERY WIRING DIAGRAM Figure 5 3 1 4 2 ...
Page 32: ...27 KEOR T 40 60kVA 2x60pcs 7 9Ah BATTERY WIRING DIAGRAM Figure 5 3 1 4 3 ...
Page 33: ...28 KEOR T 40 60kVA 3x60pcs 7 9Ah BATTERY WIRING DIAGRAM Figure 5 3 1 4 4 ...
Page 46: ...41 Appendix 3 Description of UPS and Block Diagram SEPARATED RECTIFIER AND BYPASS INPUTS ...