![LEGRAND 30 KVA Installation Manual Download Page 16](http://html.mh-extra.com/html/legrand/30-kva/30-kva_installation-manual_1872147016.webp)
11
5. INSTALLATION
When the UPS is delivered, examine the packaging and product carefully to see if any damage occured during transport.
If either possible or ascertained damage is found report it immediately to:
•
the carrier;
•
LEGRAND Technical Assistance Center.
Make sure that the unit received corresponds to the material specified on the delivery document. The UPS Keor T
packaging protects the equipment against mechanical and environmental damages. For greater protection it is also
wrapped in a transparent film.
Check if the following are provided with the equipment
•
UPS
•
Operating Manual
•
Installation Manual
•
Key for door
•
Battery fuses (three pieces)
•
Plinths
5.1. Models and Dimensions
Legrand
Reference
UPS
Type
Dimension
(HxWxD)
Weight
(Kgs)
Internal Batteris
Type
310200
10kVA Model 0
1345 x 400 x 800
121
No battery
310201
10kVA Model 1
1345 x 400 x 800
264
60 blocks 7 AH
310202
10kVA Model 2
1345 x 400 x 800
278
60 blocks 9 AH
310203
10kVA Model 3
1650 x 400 x 800
426
120 blocks 7 AH
310204
15kVA Model 0
1345 x 400 x 800
132
No battery
310205
15kVA Model 1
1345 x 400 x 800
272
60 blocks 7AH
310206
15kVA Model 2
1345 x 400 x 800
290
60 blocks 9 AH
310207
15kVA Model 3
1650 x 400 x 800
428
120 blocks 7 AH
310208
20kVA Model 0
1345 x 400 x 800
144
No battery
310209
20kVA Model 1
1345 x 400 x 800
286
60 blocks 7AH
310210
20kVA Model 2
1345 x 400 x 800
304
60 blocks 9 AH
310211
20kVA Model 3
1650 x 400 x 800
486
120 blocks 7 AH
310212
30kVA Model 0
1345 x 400 x 800
148
No battery
310213
30kVA Model 1
1345 x 400 x 800
309
60 blocks 9 AH
310214
30kVA Model 2
1650 x 400 x 800
455
120 blocks 7 AH
310215
30kVA Model 3
1650 x 400 x 800
491
120 blocks 9 AH
310216
40kVA Model 0
1650 x 600 x 900
241
No battery
310217
40kVA Model 1
1650 x 600 x 900
552
120 blocks 7 AH
310218
40kVA Model 2
1650 x 600 x 900
588
120 blocks 9 AH
310219
40kVA Model 3
1650 x 600 x 900
764
180 blocks 9 AH
310220
60kVA Model 0
1650 x 600 x 900
276
No battery
310221
60kVA Model 1
1650 x 600 x 900
625
120 blocks 9 AH
310222
60kVA Model 2
1650 x 600 x 900
799
180 blocks 9 AH
Table.3
Before the installation, please check if your UPS is customized following your special requirements (if
any).
Summary of Contents for 30 KVA
Page 1: ...KEOR T 10 60 KVA INSTALLATION MANUAL ...
Page 4: ...IV Installation Operating Manuals Battery Fast Fuses ...
Page 30: ...25 KEOR T 10 30kVA 1x60pcs 7 9Ah BATTERY WIRING DIAGRAM Figure 5 3 1 4 1 ...
Page 31: ...26 KEOR T 10 30kVA 2x60pcs 7 9Ah BATTERY WIRING DIAGRAM Figure 5 3 1 4 2 ...
Page 32: ...27 KEOR T 40 60kVA 2x60pcs 7 9Ah BATTERY WIRING DIAGRAM Figure 5 3 1 4 3 ...
Page 33: ...28 KEOR T 40 60kVA 3x60pcs 7 9Ah BATTERY WIRING DIAGRAM Figure 5 3 1 4 4 ...
Page 46: ...41 Appendix 3 Description of UPS and Block Diagram SEPARATED RECTIFIER AND BYPASS INPUTS ...