![LEGRAND 30 KVA Installation Manual Download Page 44](http://html.mh-extra.com/html/legrand/30-kva/30-kva_installation-manual_1872147044.webp)
39
Appendix-2: Modbus List
While reading data through MODBUS, the following addresses can be used. "03 - Read Holding Registers" must be
selected to read the MODBUS data.
We can send commands by using MODBUS. To do that function 06 – Write Single Register must be used.
The data is defined as unsigned words (2 bytes).
Address Coefficient Data Definition
Read (R) / Write (W)
100
1 L1 Input Voltage
R
101
1 L2 Input Voltage
R
102
1 L3 Input Voltage
R
103
1 L1 Input Current
R
104
1 L2 Input Current
R
105
1 L3 Input Current
R
106
0,1 Input Frequency
R
107
1 L1 Output Voltage
R
108
1 L2 Output Voltage
R
109
1 L3 Output Voltage
R
110
1 L1 Output Current
R
111
1 L2 Output Current
R
112
1 L3 Output Current
R
113
0,1 Output Frequency
R
114
1 L1 Output Load Percentage
R
115
1 L2 Output Load Percentage
R
116
1 L3 Output Load Percentage
R
117
1 L1 Bypass Voltage
R
118
1 L2 Bypass Voltage
R
119
1 L3 Bypass Voltage
R
120
1 Positive Battery String Voltage
R
121
1 Negative Battery String Voltage
R
122
1 Positive Battery String Current
R
123
1 Negative Battery String Current
R
124
1 Battery / Ambient Temperature
R
125
1 Positive DC Bus String Voltage
R
126
1 Negative DC Bus String Voltage
R
127
1 UPS Conditions and Alarms (***)
R
201
1
If "1" is sent then beeper will be on. If "0" is sent then beeper
will be off.
R/W
202
1 If "1" is sent then a battery test will start.
R/W
Summary of Contents for 30 KVA
Page 1: ...KEOR T 10 60 KVA INSTALLATION MANUAL ...
Page 4: ...IV Installation Operating Manuals Battery Fast Fuses ...
Page 30: ...25 KEOR T 10 30kVA 1x60pcs 7 9Ah BATTERY WIRING DIAGRAM Figure 5 3 1 4 1 ...
Page 31: ...26 KEOR T 10 30kVA 2x60pcs 7 9Ah BATTERY WIRING DIAGRAM Figure 5 3 1 4 2 ...
Page 32: ...27 KEOR T 40 60kVA 2x60pcs 7 9Ah BATTERY WIRING DIAGRAM Figure 5 3 1 4 3 ...
Page 33: ...28 KEOR T 40 60kVA 3x60pcs 7 9Ah BATTERY WIRING DIAGRAM Figure 5 3 1 4 4 ...
Page 46: ...41 Appendix 3 Description of UPS and Block Diagram SEPARATED RECTIFIER AND BYPASS INPUTS ...