5
3.3. Important Notice for UPS
•
The equipment may only be installed and commissioned by authorized LEGRAND UPS Technical Service Personnel.
•
This manual contains important instructions that you should follow during installation and maintenance of the UPS
and batteries. Please read all instructions before installing the equipment and save this manual for future reference.
•
Not obeying the instructions written on this manual which may result with possible injury of the operator or
damage of the equipment.
•
The equipment shall be packed properly during transportation and proper equipment should be used for
transportation. Never transport in horizontal position.
•
The UPS must always stands in a vertical position. Make sure that the floor can support the weight of the system.
•
Connect the PE ground connector before connecting any other cable.
•
UPS is designed for indoor use. To reduce the risk of fire or electric shock, install this UPS in a temperature and
humidity controlled indoor environment, free of conductive contaminants. Ambient temperature must not exceed
40°C (104°F). Do not operate near water or excessive humidity (95% maximum without condensation).
•
UPS requires 3Ph-N+PE input connection.
•
Do not connect the output neutral to the protective ground or protective bounding (except the TNC Option). Keor T
does not modify the neutral arrangements of the system; the use of an isolation transformer is required should it
be necessary to modify the neutral arrangements downstream Keor T.
•
KEOR T must be protected from voltage surge with devices that are suited to the installation; the mains voltage
surge must be limited to 2kV. These protective devices must be sized to take into account all the installation
parameters (geographical position whether or not there is a lightning rod, whether or not there are other
suppressors in the electrical installation, etc )
•
Even when connections removed, residual voltages of capacitors and/or high temperature may exist on connection
terminals and inside the UPS. Before working on terminals, check between all the terminals included PE that no
hazardous voltages exist.
•
The connections shall be made with cables of appropriate cross-section in order to prevent the risk of fire. All
cables shall be of insulated type and shall not be laid out on the walking path of the persons.
•
Contact your local recycling or hazardous waste center for information on proper disposal of the used battery or
UPS.
•
Make sure that the UPS is not overloaded to provide a higher quality supply to the loads.
•
In case of an extraordinary situation (damaged body, cabinet or connections, penetration of foreign materials into
the body or cabinet etc.) de-energize the UPS immediately and consult to the LEGRAND Technical Assistance Center.
•
When used for particular applications such as life support systems or any other application where product failure is
likely to cause substantial harms to person, we would advise you to contact LEGRAND UPS to confirm the ability of
these products to meet the requested level of safety, performance, reliability and compliance with applicable laws,
regulations and specifications.
Summary of Contents for 30 KVA
Page 1: ...KEOR T 10 60 KVA INSTALLATION MANUAL ...
Page 4: ...IV Installation Operating Manuals Battery Fast Fuses ...
Page 30: ...25 KEOR T 10 30kVA 1x60pcs 7 9Ah BATTERY WIRING DIAGRAM Figure 5 3 1 4 1 ...
Page 31: ...26 KEOR T 10 30kVA 2x60pcs 7 9Ah BATTERY WIRING DIAGRAM Figure 5 3 1 4 2 ...
Page 32: ...27 KEOR T 40 60kVA 2x60pcs 7 9Ah BATTERY WIRING DIAGRAM Figure 5 3 1 4 3 ...
Page 33: ...28 KEOR T 40 60kVA 3x60pcs 7 9Ah BATTERY WIRING DIAGRAM Figure 5 3 1 4 4 ...
Page 46: ...41 Appendix 3 Description of UPS and Block Diagram SEPARATED RECTIFIER AND BYPASS INPUTS ...