30
FLUSH-MOUNTING
CABINETS
1
INSERTING OF THE CABLES/
CABLES ENTRY
The XL³ S 160 are fitted with knockout
cable entries in order to mount cable
glands ISO 25 and/or ISO 32:
■
Number of cylindrical entries
- 24 modules: 14 entries Ø 25 and 7
entries Ø 32
- 36 modules: 20 entries Ø 25 and 10
entries Ø 32
Ø 32 mm
Ø 25 mm
It’s also possible to cut rectangular
areas to allow the circulation of several
sleeves.
The angles are pre-marked on the top
and at the bottom of the cabinet. The
cutting is done using a jigsaw or a tube
cutter.
■
Number of rectangular entries
Number
of
modules
Rectangular knockout
entries
Number and dimension
24
7 (62x80) mm
36
10 (62x80) mm
2
PROTECTIVE CONDUCTORS AND IP
2X DISTRIBUTION TERMINAL BLOCKS
First, you need to fit the mounting lugs
which are supplied with the cabinet
(2 lugs) by using the nuts.
Mounting lug
Mounting nut (tightening with
a 10 mm spanner
The brass terminal block Cat. No
0 373 00 that is fixed on the lugs supplied
with the cabinet (with the 2 screws and 2
nuts supplied with the Cat. No 0 373 00).
4 positions in the cabinets are possible.
→ 2 at the top and/or 2 at the bottom.
Here is example with 2 earth terminal
blocks at the top of the cabinet.
Wiring and connection