13
DISTRIBUTION CABINETS
XL
3
S 160
2
DPX³ 160 MOUNTING
The rail must be placed in the low
position and the DPX³ must be equipped
with the corresponding adapters:
- Cat.no 4 210 68 for DPX³ 160 with side
motor drive
- Cat.no 4 210 71 for DPX³ 160 with no
side motor drive
- Cat.no 4 210 73 for DPX³ 160 with earth
leakage modules with no side motor
drive
Remove the rail by loosening the 2
screws with a Torx T30 end cap:
Twist both lugs (using pliers) outwards
as far as possible so as to fold them into
the uprights:
Before
After
Install the height kit Cat.no 3 374 07 on
both sides using the screws supplied
(take the fixing holes circled in red
below):
Kit Cat.no 3 374 07
Fixing holes
Kit installed on a side
Replace the rail with the 2 screws in
the holes provided and then install the
product.
Modular devices (MCB) can be mounted
next to a DPX³ 160. For this purpose,
the rail extension Cat.no 3 382 40 must
be used. After cutting it to length (if
required), it must be clipped onto the top
hat rail next to the DPX³.
The depth is then correct to allow the
faceplate to be fitted.
It is also possible to combine a
DRX 125 and a DPX³ 160 in the
same row by mounting the DRX
(with its adapter) on the extension Cat.no
3 382 42.
The rail must be in the low position (see
paragraph 2).
The mounting of the DPX³ 160 is detailed
in section 2.