21
DISTRIBUTION CABINETS
XL
3
S 160
2
FLUSH-MOUNTING
It’s only possible by fixing the cabinet in a masonry wall (cinder block, engineering/
plain brick and aerated concrete) or a partition in hard materials (partition brick,
precast plaster blocks and aerated concrete) associated to isolation in many cases.
Cabinets can be fixed using plaster, adhesive mortar or cement, as required.
■
Flush-mounting dimensions of the 24 and 36 modules cabinets
Cat. Nos
A
B
C
24
modules
3 372 22
595
440
135
3 372 23
590
595
3 372 24
740
595
3 372 25
811
740
3 372 26
890
595
3 372 27
890
811
3 372 28
1040
595
36
modules
3 372 34
1040
811
135
3 372 35
1190
595
3 372 36
1190
811
3 372 37
1340
595
3 372 38
1340
811
The flush-mounting width must be expanded at the masonry anchors (+ 35mm in
width per anchor).
Dimension B + 70mm
The hole in the masonry wall must have a minimum depth of 135 mm.
The set par isolation must have a minimum depth of 135 mm, including a
minimum depth of 100 mm for the partition. (The anchors sealing is made at mid-depth
of the cabinet, i.e. approximately 70 mm).