Legrand PDU User Guide 245
Server Status Checking or Power Control
It is model dependent whether your Legrand PDU supports the shutdown and power control features via
the Server Reachability page.
After adding IT equipment for monitoring, all IT devices are listed on the Server Reachability page.
In the beginning, the status of the added IT equipment shows "Waiting for reliable connection," which means
the requested number of consecutive successful or unsuccessful pings has not reached before Legrand PDU
can declare that the monitored device is reachable or unreachable.
To check the server monitoring states and results:
1. The column labeled "Ping Enabled" indicates whether the monitoring for the corresponding IT device is
activated or not.
2. The column labeled "Status" indicates the accessibility of monitored equipment.
Status
Description
Reachable
The monitored equipment is accessible.
Unreachable
The monitored equipment is inaccessible.
Waiting for reliable
connection
The connection between the Legrand PDU
device and the monitored equipment is not
reliably established yet.
3. If your Legrand PDU supports outlet switching, one more column displays --
Power Control
.
Power control
status
Description
(disabled)
Power control is not enabled for the monitored
equipment.
Server power is on The outlet or outlet group associated with the
monitored equipment is being powered on.
In the scenario where an 'outlet group' is
associated with the equipment, the message
'Server power is on' is shown as long as one
of the outlets in the outlet group remains
powered on.
Server power is off The outlet or all outlets of the outlet group
associated with the monitored equipment are
being powered off.
Server is shutting
down
Legrand PDU has sent the shutdown command
to the monitored equipment, but the shutdown
operation has not completed or succeeded yet.