   7 .  COMMUNICATION OBJECTS (continued)

7 .3 "Weather alarms" parameter (continued)

Monitoring period for rain alarm in s

[0…1000]

*0

…1000

The telegram of the active weather station is monitored cyclically. The 

actuator waits for a telegram from the weather station within the cycle 

time. If the telegram is not received within this monitoring period 

time, actuator assumes that the weather station is broken or bus line is 

damaged and the blind moves into the parameterized position.
    • 

0

: If “

0

” is selected cyclically monitoring is deactivated. If the alarm 

telegram value is “

1

”, weather alarm is activated.

Frost alarm

*disable

 

 enable

This parameter activates the frost alarm. If the parameter selected 

enable

”, “

Monitoring period for frost alarm in s [0…1000]

” 

parameter is visible.

Monitoring period for frost alarm in s 

[0…1000]

*0

…1000

The telegram of the active weather station is monitored cyclically. The 

actuator waits for a telegram from the weather station within the cycle 

time. If the telegram is not received within this monitoring period 

time, actuator assumes that the weather station is broken or bus line is 

damaged and the blind moves into the parameterized position.
    • 

0

: If “

0

” is selected cyclically monitoring is deactivated. If the alarm 

telegram value is “

1

”, weather alarm is activated.

7 .4 List of scene

The scene function of the switch actuator has an 8 bit scene object. You 

can define for each 64 scene with parameter window. 8 independent 

values can be stored for each relay or each blind. The scene can be 

specified that the relay OFF (open contact), or ON (close contact) its 

state for switch function. If you use the blind, you can configure the 

blind height and slat position. You can save height position for blind 

also slat-opening angle as scene values. 
When the actuator receives a telegram that retrieves a scene address:

• The output group is configured as a blind, the drive is moved into the 

saved position and slats are turned. 

• The output group is configured as a switch, the actuator evaluate the 

transmitted scene address and switches the output to the stored scene 

value.

A scene is activated when it receives its scene number at the scene 

object. The storing of the current channel values is carried out using the 

scene object.
For example:

Scene

recall

save

Hex .

Des .

Hex .

Des .

1

0x00

0

0x80

128

2

0x01

1

0x81

129

3

0x02

2

0x82

130

4

0x03

3

0x83

131

5

0x04

4

0x84

132

6

0x05

5

0x85

133

7

0x06

6

0x86

134

8

0x07

7

0x87

135

9

0x08

8

0x88

136

10

0x09

9

0x89

137

11

0x0A

10

0x8A

138

63

0x3E

62

0xE2

190

64

0x3F

63

0xE3

191

   7 .  COMMUNICATION OBJECTS (continued)

7 .4 List o List of scene f scene (continued)

Overwrite scene on download

  no

*yes

This parameter is selected the reaction of the scene set.

• Set the parameter to “no”;
During storage of a scene, the scene values are stored in the device. If 

you want to protect your scene in the device, you are selected “no”.

•  Set the parameter to “yes”;
The original ETS parameter values can be reload into the device 

during ETS download operation.

1…64 scene number (0 = no assignment)

*0

…64

This parameter is used to following parameter belongs to which 

scene. 0 meaning following parameters are not belong to any scene.

Blind position value in %[100]

*0

…100

Slat position value in %[100]

*0

…100

Value

*OFF

  ON

These parameters are the common of the blind and switch. 

• If the “Output group A” 

is selected

 “2 x switch”, scene parameters 

mean the switch state ON/OFF. 

• If the “Output group A” 

is selected

 “1 x blind”, scene parameters 

mean blind height and slat position. 

If the blind type is selected roller shutter, slat position parameter 

is invalid.  0%: open blind, 100%: bottom blind also you can select 

between %0 – %100 values. This parameter is used for parameterizing 

the blind position, which is executed when the scene is recalled.

7 .5 "Enable Input a…s" parameter

Input a…s

*no function

  switch sensor

  switch dim sensor

  shutter sensor

  value operation

This parameter is used to select input function.

• This parameter is selected “switch sensor”
Distinction between short/long operation and cyclical sending.

• This parameter is selected “switch dim sensor”
Start-stop dimming and stepwise dimming are possible.

• This parameter is selected “shutter sensor”
For movement/louvre adjustment of a blind or a shutter.

• This parameter is selected “value operation”
It is possible to send different values or data point types.

CONTENTS

Summary of Contents for 0 026 72

Page 1: ...ch Sensor parameter 10 7 5 2 a Switch Dim Sensor parameter 11 7 5 2 a Switch Dim Sensor parameter continued 11 7 5 3 a Blind Sensor parameter 11 7 5 4 a Value Forced Operation parameter 12 7 6 Enable...

Page 2: ...n parameter 23 7 10 2 A B1 Status Message parameter 24 7 10 3 A B1 Automatic Operation parameter 25 7 10 4 A B1 Direct Mode parameter 25 7 11 Function Chart 26 7 12 Object Description 26 7 12 1 Genera...

Page 3: ...ut x4 AC Blind x2 DC Blind x1 2 Point valve x2 3 point valve x2 Suitable for switching resistive capacitive and inductive loads as well as fluorescent lamp loads according to EN 60 669 A single switch...

Page 4: ...4123EN 1 Updated Created 18 01 2021 Cat No s 0 026 72 73 74 76 78 79 KNX controller multi application DIN 4 CONNECTION 0 026 72 73 AC Motor D2 NA Fan1 Fan2 Fan3 4 CONNECTION continued 0 026 74 AC Moto...

Page 5: ...ted 18 01 2021 Cat No s 0 026 72 73 74 76 78 79 KNX controller multi application DIN 4 CONNECTION continued 0 026 76 AC Motor AC Motor DC Motor F G DC Motor F G 4 CONNECTION continued 0 026 78 79 AC M...

Page 6: ...S4 or higher Important A detailed information about parameter configuration can be found in Product Manual of device Installation and commissioning of device may only be implemented by trained electri...

Page 7: ...100 1 bit CW 98 Output A1 Staircase lighting duration 7 007 2 byte CRW Output A Output A B Move to position height 0 255 5 001 1 byte CW Fan A B1 Switch speed 3 1 001 1 bit CW Control input Fault con...

Page 8: ...e sent freely within a period Note If the value of the object cannot be sent in the time of a period The object is buffered for the next period time The buffered object will be updated if the object v...

Page 9: ...valuate the transmitted scene address and switches the output to the stored scene value A scene is activated when it receives its scene number at the scene object The storing of the current channel va...

Page 10: ...is distinction between short and long operation The contact type of the push button attached to the channel is adjusted here Cyclic transmission of object no switch OFF switch ON always This paramete...

Page 11: ...operation STOP telegram sends at the end of operation Brightness change on every sent telegram 100 6 25 1 56 This parameter is only visible with the Dimming steps options This parameter is cyclically...

Page 12: ...op command is sent such as STOP Lamella adj UP or STOP Lamella adj DOWN 1 Shutter MOVE UP STOP Lamella UP 2 Shutter MOVE DOWN STOP Lamella DOWN 2 button stepping On operation Stop lamella adjustment T...

Page 13: ...n shutter blind DC fan coil valve control individually Both output group can be combined into one DC blind In DC blind operation the four relay contacts of the device can be used to control electrical...

Page 14: ...bus voltage return Behavior bus voltage failure keep position open contact close contact When the bus voltage fails the device set the wanted switching state of the output The relay can be open close...

Page 15: ...mber of pre warning and time for pre warning interval The warning function is for warning that the staircase lighting time run out and the lights are switched off soon In the warning lights short turn...

Page 16: ...B General parameter continued Behavior after ETS programming or after ETS reset Behavior bus voltage failure no reaction up down stop position 1 2 3 4 approach position This parameter can be used to c...

Page 17: ...e Trigger reference movement communication object is visible The reference movement is triggered via this communication object In long time slight inaccuracies can occur so the upper and lower end pos...

Page 18: ...This function allows you set a height position or slat position directly using with communication object Enable communication objects Move to pos Height Move slat 0 255 no yes The communication Move t...

Page 19: ...havior in case of rain alarm Behavior in case of frost alarm no reaction up down stop position 1 position 2 position 3 position 4 individual position When the alarm is activated the blind moves this p...

Page 20: ...tion communication object is updated After the bus voltage return forced position function set to the parametrized position Set the parameter to no forced position active The forced operation is deact...

Page 21: ...ING is deactivated Set the parameter to 1 When the telegram is received 1 HEATING operation is activated COOLING is deactivated Monitoring control valves yes no This parameter activate the thermostat...

Page 22: ...vel time This time is maximum one minute Valve limitation yes no The limitation of the control value limits the height of the control value The limitation is activated when a value is chosen which is...

Page 23: ...ons Thus initially the number of fan levels required for the connected devices can be defined The number of fan levels can be specified separately for each fan coil channel Controlling the fan levels...

Page 24: ...ime has elapsed 7 COMMUNICATION OBJECTS continued 7 10 Fan Coil parameter continued 7 10 2 A B1 Status Message parameter Enable communication object Status fan speed x 1 bit yes no The data format for...

Page 25: ...peed In s 0 65535 0 65535 This parameter defines the dwell time for a fan speed of the fan until it switches to the next higher or lower fan speed 0 no delay time for switching 7 COMMUNICATION OBJECTS...

Page 26: ...x Des 1 0x00 0 0x80 128 2 0x01 1 0x81 129 3 0x02 2 0x82 130 4 0x03 3 0x83 131 5 0x04 4 0x84 132 6 0x05 5 0x85 133 7 0x06 6 0x86 134 8 0x07 7 0x87 135 9 0x08 8 0x88 136 10 0x09 9 0x89 137 11 0x0A 10 0x...

Page 27: ...d operation 1 byte 0 255 DPT 5 001 brightness value 2 byte 32768 32767 DPT 7 001 signed value 2 byte 0 65535 DPT 8 001 unsigned value 4 byte float value DPT14 068 temperature 4 byte 0 4294967295 DPT12...

Page 28: ...or 4 104 Trigger reference movement Output A DTP 1 008 1 bit CW This object is triggered the reference movement If the telegram is received the blind is moved up or down end position Then the blind c...

Page 29: ...OMMUNICATION OBJECTS continued 7 17 Fan Object Description No Object name Name DTP Type Length Flags 95 Fan speed switch Fan DPT 5 010 1 byte CW This object is used to switch on fan speed via 1 byte o...

Reviews: