Technical data sheet: S000114123EN-1
Updated:
Created: 18/01/2021
Cat. No(s): 0 026 72/73/74/76/78/79
KNX controller multi-application DIN
7 . COMMUNICATION OBJECTS (continued)
7 .5 "Enable Input a…s" parameter (continued)
7 .5 .4 "a - Value/Forced Operation" parameter (continued)
Reaction on operation
no reaction
1-bit value
2-bit value (forced operation)
*1 byte value [0…255]
2 byte [-32768…32767]
2 byte [0…65535]
4 byte (floating point)
4 byte value [0…4294967295]
This parameter is visible no distinction short/long operation;
This parameter determines the data type.
When button is pressed, this type of data sent KNX line with the
communication object.
Reaction on short operation
no reaction
1-bit value
2-bit value (forced operation)
*1 byte value [0…255]
2 byte [-32768…32767]
2 byte [0…65535]
4 byte (floating point)
4 byte value [0…4294967295]
This parameter is visible distinction short/long operation; when
button is pressed, this value sends KNX line on the communication
object.
Transmitted value
* Dependent on the selection made at
reaction on operation .
Short press value or on operation value is enter here.
Reaction on long operation
no reaction
1-bit value
2-bit value (forced operation)
*1 byte value [0…255]
2 byte [-32768…32767]
2 byte [0…65535]
4 byte (floating point)
4 byte value [0…4294967295]
This parameter is visible distinction short/long operation;
This parameter determines the data type.
When button is pressed, this type of data sent KNX line with the
communication object.
Transmitted value (long press)
* Dependent on the selection made at
reaction on operation .
This parameter is visible distinction short/long operation;
Short press value or on operation value is enter here.
Long operation after:
Time base
*250ms
1s
10s
1min
10min
This parameter is visible distinction short/long operation;
This parameter determines the desired long press time.
Period time: Base x Factor
Factor
1…
*4
…255
Select time factor, between [1…255]
Transmit object value after bus voltage
recovery .
yes
*no
This parameter is visible no distinction short/long operation;
In the event of power supply failure to the electronics, the value (if this
can be changed via a communication object) is permanently stored in
a memory protected against data loss in the event of voltage failure.
They are transferred from this memory into the working memory on
bus voltage recovery.
Debounce time
10ms…
*50ms
…150ms
Debounce uses the input, which means checking twice in a short
period of time to make sure it’s definitely pressed.
7 . COMMUNICATION OBJECTS (continued)
7 .6 "Enable Output A…J" parameter
Output group A and B
*no function
shutter/blind DC
fan coil
valve control
individually
Both output group can be combined into one DC blind. In DC blind
operation the four relay contacts of the device can be used to control
electrically AC blind, shutter, awning, and venetian blind. Depending
on this setting, all the group parameters and objects are created in the
ETS.
• Set the parameter to “
no function
”
The parameter is selected output group A and B are invisible. You can
not configured this channels.
• Set the parameter to “
shutter/blind DC
”;
The appropriate output quad is configured to DC blind. Four outputs
are combined into one blind channel. In the blind mode four relay
are locked against each other. The DC blind can be used to control
electrically driven blinds, shutters, awnings and venetian blinds. DC
blind operation page name starts with A/B, C/D prefix. The names of
the output objects and the parameter page change accordingly.
• Set the parameter to “
fan coil
”:
The appropriate output three is configured to fan. Three outputs
are combined into one fan channel. In the fan mode three relay are
locked against each other. One output can not used by user.
• Set the parameter to “
valve control
”:
Valve control channel has a two valve. They can be configured
separately 3-point or 2-point.
3-point valve drives are normally connected via three connection
cables to the device: Neutral conductor, switched phase to OPEN,
switched phase for CLOSE. Using 3-point control value drives, the
valve can be opened by any desired percentage and the position can
be retained over an extended period. If the valve does not move, no
voltage is applied to the motor.
2-point valve drives are controlled via the telegrams OPEN and
CLOSE. The valve can only be completely open or completely closed.
• Set the parameter to “individually”:
The parameter is selected “AC motor or switch” and the “Output
group A” and “Output group B” parameters become visible. You can
configured each output group separately.
Output group A
*shutter/blind AC
2 x switch
Output group B
* shutter/blind AC
2 x switch
The appropriate output pair is configured by this parameter.
• Set the parameter to “
shutter/blind AC blind
”:
The appropriate output pair is configured to AC blind. Two outputs
are combined into one blind channel. In the blind mode two relay
are locked against each other. The AC blind can be used to control
electrically driven blinds, shutters, awnings and venetian blinds.
AC blind operation page name starts with A, B, C and D prefix.
The names of the output objects and the parameter page change
accordingly.
• Set the parameter to “
2 x switch
”;
• The appropriate output is configured to switch operation. Switch
operation page name starts with A1, A2, B1… D1 and D2 prefix.
The names of the output objects and the parameter page change
accordingly.