LEGRAND 0 026 72 Manual Download Page 29

29/29

Technical data sheet: S000114123EN-1 

Updated: 

Created: 18/01/2021

Cat. No(s): 0 026 72/73/74/76/78/79

KNX controller multi-application DIN

   7 .  COMMUNICATION OBJECTS (continued)

7 .16 Valve Object Description

No

Object name

Name

DTP Type

Length Flags

95

Control valve HEATING

Control Input

DPT 5.001

1 byte

CW

Via this object, command value for heating operation is sent. 

96

Control valve COOLING

Control Input

DPT 5.001

1 byte

CW

Via this object, command value for cooling operation is sent. 

97

Toggle Heating/Cooling

Control Input

DPT 1.100

1 bit

CW

If the HVAC System parameter has been selected one control four pipe with switch or two 

control two pipe with switch, this object is enabled.

If the parameter Object value for HEATING the object is selected 1:

1 : HEATING

0 : COOLING

If the parameter Object value for HEATING the object is selected 0:

1 : COOLING

0 : HEATING

98

Fault control value

Control Input

DPT 1.005

1 bit

CRT

If the control input telegram does not arrive in the monitoring period, this object set TRUE and 

send to bus.

0 : no fault

1 : fault

99

Block

Valve HEATING

Valve COOLING

DPT 1.003

1 bit

CW

This object is used to block the valve operation. The valve does not respond any control input 

values.

100

Forced operation

Valve HEATING

Valve COOLING

DPT 1.003

1 bit

CW

This object is used to force the valve-desired state. This state can be configure via Value 

position on forced operation in % [0…100] parameter.

0 : end of forced operation

1: start of forced operation

101

Trigger valve purge

Valve HEATING

Valve COOLING

DPT 1.017

1 bit

CW

This object is use to triggered the valve purge.

0 : end of valve purge

1: start of valve purge

102

Status valve purge

Valve HEATING

Valve COOLING

DPT 1.003

1 bit

CRT

The status of the valve purge is visible via this communication object.

103

Status valve position

Valve HEATING

Valve COOLING

DPT 1.001

DPT 1.005

1 bit

1 byte

CRT

The status of valve position is visible vis this communication object.
If the object is configured 1-bit:

0 : valve position is zero

1 : valve position is not zero
If the object is configured 1 byte:

0…255 : valve position is show via percentage

   7 .  COMMUNICATION OBJECTS (continued)

7 .17 Fan Object Description

No

Object name

Name

DTP Type

Length Flags

95

Fan speed switch

Fan

DPT 5.010

1 byte

CW

This object is used to switch on fan speed via 1-byte object. If the object received, automatic 

mode is set OFF.

Hex Fan Speed

00 0 (Fan OFF)
01       Fan speed 1
02       Fan speed 2
03 Fan speed 3

>03 ignored

96

Switch speed 1

Fan

DPT 1.001

1 bit

CW

97

Switch speed 2

Fan

DPT 1.001

1 bit

CW

98

Switch speed 3

Fan

DPT 1.001

1 bit

CW

This object is used to receive a control value for fan speed. An OFF telegram to one of the three 

communication objects, fan speed 1-3, switch off the fan completely. If the object received, 

automatic mode is set OFF.

0 : fan OFF

1 : fan ON

99

Fan speed UP/DOWN

Fan

DPT 1.007

1 bit

CW

This object is used to switched one fan speed further up or down via 1-bit telegram.

0 : fan speed DOWN

1 : fan speed UP

100

Status fan ON/OFF 

Fan

DPT 1.001

1 bit

CT

The status of fan coil channel is visible via this communication object.

0 : complete fan coil channel inactive (all outputs OFF)

1 : any output of fan coil channel is switched ON

101

Status fan speed

Fan

DPT 5.010

1 byte

CRT

This object is used to display the fan speed via 1-byte object.

Hex Fan Speed

00 0 (Fan OFF)
01       Fan speed 1
02       Fan speed 2
03 Fan speed 3

102

Status fan speed 1

Fan

DPT 1.001

1 bit

CRT

103

Status fan speed 2

Fan

DPT 1.001

1 bit

CRT

104

Status fan speed 3

Fan

DPT 1.001

1 bit

CRT

Only visible if the Enable communication object “Status fan speed x” 1 bit is configured to yes.

0 : fan level x deactivated

1 : fan level x activated

105

Forced operation

Fan

DPT 1.003

1 bit

CW

This object used to set fan desired forced position independently from the control value.

0 : no forced operation

1 : forced operation

106

Automatic ON/OFF

Fan

DPT 1.003

1 bit

CW

This object is used to switch the automatic mode. Automatic mode is switched off, if a telegram 

is received on a direct communication object.

If the object value “

automatic ON/OFF

” switched on to automatic parameter is selected “

1

”:

0 : automatic operation OFF

1: automatic operation ON

If the object value “

automatic ON/OFF

” switched on to automatic parameter is selected “

0

”:

0 : automatic operation ON

1: automatic operation OFF

107

Status automatic

Fan

DPT 1.003

1 bit

CW

The object indicates the status of the automatic mode.

0 : inactive

1 : active

CONTENTS

Summary of Contents for 0 026 72

Page 1: ...ch Sensor parameter 10 7 5 2 a Switch Dim Sensor parameter 11 7 5 2 a Switch Dim Sensor parameter continued 11 7 5 3 a Blind Sensor parameter 11 7 5 4 a Value Forced Operation parameter 12 7 6 Enable...

Page 2: ...n parameter 23 7 10 2 A B1 Status Message parameter 24 7 10 3 A B1 Automatic Operation parameter 25 7 10 4 A B1 Direct Mode parameter 25 7 11 Function Chart 26 7 12 Object Description 26 7 12 1 Genera...

Page 3: ...ut x4 AC Blind x2 DC Blind x1 2 Point valve x2 3 point valve x2 Suitable for switching resistive capacitive and inductive loads as well as fluorescent lamp loads according to EN 60 669 A single switch...

Page 4: ...4123EN 1 Updated Created 18 01 2021 Cat No s 0 026 72 73 74 76 78 79 KNX controller multi application DIN 4 CONNECTION 0 026 72 73 AC Motor D2 NA Fan1 Fan2 Fan3 4 CONNECTION continued 0 026 74 AC Moto...

Page 5: ...ted 18 01 2021 Cat No s 0 026 72 73 74 76 78 79 KNX controller multi application DIN 4 CONNECTION continued 0 026 76 AC Motor AC Motor DC Motor F G DC Motor F G 4 CONNECTION continued 0 026 78 79 AC M...

Page 6: ...S4 or higher Important A detailed information about parameter configuration can be found in Product Manual of device Installation and commissioning of device may only be implemented by trained electri...

Page 7: ...100 1 bit CW 98 Output A1 Staircase lighting duration 7 007 2 byte CRW Output A Output A B Move to position height 0 255 5 001 1 byte CW Fan A B1 Switch speed 3 1 001 1 bit CW Control input Fault con...

Page 8: ...e sent freely within a period Note If the value of the object cannot be sent in the time of a period The object is buffered for the next period time The buffered object will be updated if the object v...

Page 9: ...valuate the transmitted scene address and switches the output to the stored scene value A scene is activated when it receives its scene number at the scene object The storing of the current channel va...

Page 10: ...is distinction between short and long operation The contact type of the push button attached to the channel is adjusted here Cyclic transmission of object no switch OFF switch ON always This paramete...

Page 11: ...operation STOP telegram sends at the end of operation Brightness change on every sent telegram 100 6 25 1 56 This parameter is only visible with the Dimming steps options This parameter is cyclically...

Page 12: ...op command is sent such as STOP Lamella adj UP or STOP Lamella adj DOWN 1 Shutter MOVE UP STOP Lamella UP 2 Shutter MOVE DOWN STOP Lamella DOWN 2 button stepping On operation Stop lamella adjustment T...

Page 13: ...n shutter blind DC fan coil valve control individually Both output group can be combined into one DC blind In DC blind operation the four relay contacts of the device can be used to control electrical...

Page 14: ...bus voltage return Behavior bus voltage failure keep position open contact close contact When the bus voltage fails the device set the wanted switching state of the output The relay can be open close...

Page 15: ...mber of pre warning and time for pre warning interval The warning function is for warning that the staircase lighting time run out and the lights are switched off soon In the warning lights short turn...

Page 16: ...B General parameter continued Behavior after ETS programming or after ETS reset Behavior bus voltage failure no reaction up down stop position 1 2 3 4 approach position This parameter can be used to c...

Page 17: ...e Trigger reference movement communication object is visible The reference movement is triggered via this communication object In long time slight inaccuracies can occur so the upper and lower end pos...

Page 18: ...This function allows you set a height position or slat position directly using with communication object Enable communication objects Move to pos Height Move slat 0 255 no yes The communication Move t...

Page 19: ...havior in case of rain alarm Behavior in case of frost alarm no reaction up down stop position 1 position 2 position 3 position 4 individual position When the alarm is activated the blind moves this p...

Page 20: ...tion communication object is updated After the bus voltage return forced position function set to the parametrized position Set the parameter to no forced position active The forced operation is deact...

Page 21: ...ING is deactivated Set the parameter to 1 When the telegram is received 1 HEATING operation is activated COOLING is deactivated Monitoring control valves yes no This parameter activate the thermostat...

Page 22: ...vel time This time is maximum one minute Valve limitation yes no The limitation of the control value limits the height of the control value The limitation is activated when a value is chosen which is...

Page 23: ...ons Thus initially the number of fan levels required for the connected devices can be defined The number of fan levels can be specified separately for each fan coil channel Controlling the fan levels...

Page 24: ...ime has elapsed 7 COMMUNICATION OBJECTS continued 7 10 Fan Coil parameter continued 7 10 2 A B1 Status Message parameter Enable communication object Status fan speed x 1 bit yes no The data format for...

Page 25: ...peed In s 0 65535 0 65535 This parameter defines the dwell time for a fan speed of the fan until it switches to the next higher or lower fan speed 0 no delay time for switching 7 COMMUNICATION OBJECTS...

Page 26: ...x Des 1 0x00 0 0x80 128 2 0x01 1 0x81 129 3 0x02 2 0x82 130 4 0x03 3 0x83 131 5 0x04 4 0x84 132 6 0x05 5 0x85 133 7 0x06 6 0x86 134 8 0x07 7 0x87 135 9 0x08 8 0x88 136 10 0x09 9 0x89 137 11 0x0A 10 0x...

Page 27: ...d operation 1 byte 0 255 DPT 5 001 brightness value 2 byte 32768 32767 DPT 7 001 signed value 2 byte 0 65535 DPT 8 001 unsigned value 4 byte float value DPT14 068 temperature 4 byte 0 4294967295 DPT12...

Page 28: ...or 4 104 Trigger reference movement Output A DTP 1 008 1 bit CW This object is triggered the reference movement If the telegram is received the blind is moved up or down end position Then the blind c...

Page 29: ...OMMUNICATION OBJECTS continued 7 17 Fan Object Description No Object name Name DTP Type Length Flags 95 Fan speed switch Fan DPT 5 010 1 byte CW This object is used to switch on fan speed via 1 byte o...