7 . COMMUNICATION OBJECTS (continued)
7 .11 Function Chart
The following schematic indicates the function sequence. The functions
are processed. Communication object enter the left side. Same box
meaning same priority.
Object input
Functions sequence
Object ouput
7 . COMMUNICATION OBJECTS (continued)
7 .12 Object Description
7 .12 .1 General Object Description
No
Object name
Name
DTP Type
Length Flags
0
In operation
General
DPT 1.002
1 bit
CWT
You use this object to report device still alive and contacted the KNX line. Telegram value
is select ON/OFF. If a telegram is not received, device may be defective or KNX cable will be
interrupted. This communication object sends to the line cyclically.
1
Scene 8 bit
General
DPT 18.001
1 byte
CW
This object is used to recall or store scenes. Up to 64 scenes are available on the Switch/Blind
Actuator.
B r U U U U U U
C R Scene-Number
C: 0 – recall scene
1 – store scene
R: Reserved
The object to recall and store the scene (1…64) is sent via the group address. 8-bit scenes are
stored in the Switch/Blind Actuator.
Scene
recall
save
Hex .
Des .
Hex .
Des .
1
0x00
0
0x80
128
2
0x01
1
0x81
129
3
0x02
2
0x82
130
4
0x03
3
0x83
131
5
0x04
4
0x84
132
6
0x05
5
0x85
133
7
0x06
6
0x86
134
8
0x07
7
0x87
135
9
0x08
8
0x88
136
10
0x09
9
0x89
137
11
0x0A
10
0x8A
138
…
…
…
…
…
63
0x3E
62
0xE2
190
64
0x3F
63
0xE3
191
2
Disable/enable man. operation
General
DPT 1.003
1 byte
CRW
The manual operation can be enabled or disabled with this communication object. If the
manual operation is disabled, the manual control button cannot be enabled the manual
operation.
The object is:
0 = manual button enabled
1 = manual operation cannot be enabled by the button.
3
4
5
Wind alarm
Rain alarm
Frost alarm
General
DPT 1.005
1 byte CWTU
Active weather sensors can be monitored cyclically. The device expects a telegram from sensor
within the cycle time. If the telegram doesn’t receive within the cycle time or the value 1 is
received, the blinds are moved to parameterized position. The blind control telegrams are
ignored until the device is received telegram value 0.
The monitoring period is restarted each telegram is received from weather sensor. The wind
alarms are connected each other via OR gate.
The object is:
0 = no alarm
1 = alarm active
Switch
Switch
Switch status
8-bit Scene
Enable staircase func.
Scenes staircase
Priority
Relay
BUS voltage failure
BUS voltage returne
Forced positioning
External logic Switch
External logic
Internal logic
Sweep
Threshold input
Threshold Sweep