   7 .  COMMUNICATION OBJECTS (continued)

7 .5 "Enable Input a…s" parameter (continued)
7 .5 .3 "a - Blind Sensor" parameter (continued)

Operating functionality of the blind

* 1 push-button, short=stepping, 

long=moving

   1 push-button, short=moving, 

long=stepping

  1 push-button-operation, moving 

  1 switch-operation, moving

  2 push-button, standard

  2 switch-operation, moving

  2 push-button, moving

  2 push-button, stepping

• 

1 switch operation, moving

Start of operation

This property is for moving only shutters up or 

down.

While button is pressing, operation is 

continuing. This action is opposite direction to 

the last movement for moving the shutter up or 

down.

End of operation

When button releases, operation stop. 

Stop/ Lamella adj. command is send than 

movement stopped.

With below functions, you must set the parameters for a second 

key (second input) with the corresponding settings for the shutter 

movement in the opposite direction.

• 

2 button, standard

Short operation

Stop / lamella adjustment 

The stop/lamella adjustment object is 

adjustment of the lamella UP or DOWN. In 

additional it stops a running movement of the 

shutter.

Long operation

This action is for moving the chosen direction 

shutter. Movement direction is choosing on 

parameter move up or moves down.

• 

2 switch operation, moving(shutter)

Start of operation

This property is for moving only shutters up or 

down.

While button is pressing, operation is 

continuing. This action is moving the shutter 

move up

” or “

move down

”.

End of operation

When button releases, operation stop. 

Stop/ Lamella adj . UP

” or “

Stop/ Lamella 

adj . DOWN

” command is send than movement 

stopped.

You should use the property with two switches.

• 

2 switch operation, moving(shutter)

On operation

The property object “Shutter” is choose and 

performs the up‐ and down‐movement of the 

shutter.

The direction of movement depends to the 

parameters. When the button pressed firstly, 

than shutter move in direction that it was 

programmed. Second time button is pressed 

shutter stop command is sent such as STOP/

Lamella adj. UP or STOP/Lamella adj. DOWN.

1) Shutter MOVE UP 

 STOP/Lamella UP

2) Shutter MOVE DOWN 

 STOP/Lamella DOWN

• 

2 button, stepping

On operation

Stop / lamella adjustment 

The stop/lamella adjustment object is 

adjustment of the lamella UP or DOWN. Lamella 

move direction chooses on the parameters.

   7 .  COMMUNICATION OBJECTS (continued)

7 .5 "Enable Input a…s" parameter (continued)
7 .5 .3 "a - Blind Sensor" parameter (continued)

Connected contact type

  normally closed

*normally open

The contact type of the push button attached to the channel is 

adjusted here.

Reaction on short operation

*STOP/lamella UP

 

  STOP/lamella DOWN

This parameter is visible if there is distinction between short and long 

operation.

Stop/step lamella adjustment parameter. This parameter object stops 

shutter movement.

Reaction on long operation

 

 MOVE UP

 

*MOVE DOWN

Distinction between short and long:

This parameter use for choose shutter movement direction.

Long operation after

0,3s…

*0,4s

…10s

Distinction between short and long:

Long press time period is select here.

Telegr . STOP/lamella adj . is repeated every

0,3sn…

*0,4s

…10sn

Only visible 1 push-button, short=moving,

This parameter we choose each sending stop/lamella telegram-

sending period. Lamella adjustment cyclically.

Debounce time 

10ms…

*50ms

…150ms

Debounce uses the input, which means checking twice in a short 

period of time to make sure it’s definitely pressed.

7 .5 .4 "a - Value/Forced Operation" parameter

You can use these value/forced functions to parameterize different 

object actions. You can transmit one or two objects short or long press 

status sequence, and select the size of the objects required (1 bit, 2-bit 

priority control, 1 byte, 2 byte or 4 byte) as needed. This enables you to 

parameterize a large number of application options. You can enter two 

values and set whether and how they are to be transmitted short or 

long.

Connected contact type

  normally closed

*normally open

The contact type of the push button attached to the channel is 

adjusted here.

Distinction between long and short 

operation

  

yes

*no 

If the parameter is set no, the input will be evaluated normally on 

every edge of the input signal.

Yes is selected. There is a delay after opening/closing the contact to 

determine whether there is a short or long operation.

CONTENTS

Summary of Contents for 0 026 72

Page 1: ...ch Sensor parameter 10 7 5 2 a Switch Dim Sensor parameter 11 7 5 2 a Switch Dim Sensor parameter continued 11 7 5 3 a Blind Sensor parameter 11 7 5 4 a Value Forced Operation parameter 12 7 6 Enable...

Page 2: ...n parameter 23 7 10 2 A B1 Status Message parameter 24 7 10 3 A B1 Automatic Operation parameter 25 7 10 4 A B1 Direct Mode parameter 25 7 11 Function Chart 26 7 12 Object Description 26 7 12 1 Genera...

Page 3: ...ut x4 AC Blind x2 DC Blind x1 2 Point valve x2 3 point valve x2 Suitable for switching resistive capacitive and inductive loads as well as fluorescent lamp loads according to EN 60 669 A single switch...

Page 4: ...4123EN 1 Updated Created 18 01 2021 Cat No s 0 026 72 73 74 76 78 79 KNX controller multi application DIN 4 CONNECTION 0 026 72 73 AC Motor D2 NA Fan1 Fan2 Fan3 4 CONNECTION continued 0 026 74 AC Moto...

Page 5: ...ted 18 01 2021 Cat No s 0 026 72 73 74 76 78 79 KNX controller multi application DIN 4 CONNECTION continued 0 026 76 AC Motor AC Motor DC Motor F G DC Motor F G 4 CONNECTION continued 0 026 78 79 AC M...

Page 6: ...S4 or higher Important A detailed information about parameter configuration can be found in Product Manual of device Installation and commissioning of device may only be implemented by trained electri...

Page 7: ...100 1 bit CW 98 Output A1 Staircase lighting duration 7 007 2 byte CRW Output A Output A B Move to position height 0 255 5 001 1 byte CW Fan A B1 Switch speed 3 1 001 1 bit CW Control input Fault con...

Page 8: ...e sent freely within a period Note If the value of the object cannot be sent in the time of a period The object is buffered for the next period time The buffered object will be updated if the object v...

Page 9: ...valuate the transmitted scene address and switches the output to the stored scene value A scene is activated when it receives its scene number at the scene object The storing of the current channel va...

Page 10: ...is distinction between short and long operation The contact type of the push button attached to the channel is adjusted here Cyclic transmission of object no switch OFF switch ON always This paramete...

Page 11: ...operation STOP telegram sends at the end of operation Brightness change on every sent telegram 100 6 25 1 56 This parameter is only visible with the Dimming steps options This parameter is cyclically...

Page 12: ...op command is sent such as STOP Lamella adj UP or STOP Lamella adj DOWN 1 Shutter MOVE UP STOP Lamella UP 2 Shutter MOVE DOWN STOP Lamella DOWN 2 button stepping On operation Stop lamella adjustment T...

Page 13: ...n shutter blind DC fan coil valve control individually Both output group can be combined into one DC blind In DC blind operation the four relay contacts of the device can be used to control electrical...

Page 14: ...bus voltage return Behavior bus voltage failure keep position open contact close contact When the bus voltage fails the device set the wanted switching state of the output The relay can be open close...

Page 15: ...mber of pre warning and time for pre warning interval The warning function is for warning that the staircase lighting time run out and the lights are switched off soon In the warning lights short turn...

Page 16: ...B General parameter continued Behavior after ETS programming or after ETS reset Behavior bus voltage failure no reaction up down stop position 1 2 3 4 approach position This parameter can be used to c...

Page 17: ...e Trigger reference movement communication object is visible The reference movement is triggered via this communication object In long time slight inaccuracies can occur so the upper and lower end pos...

Page 18: ...This function allows you set a height position or slat position directly using with communication object Enable communication objects Move to pos Height Move slat 0 255 no yes The communication Move t...

Page 19: ...havior in case of rain alarm Behavior in case of frost alarm no reaction up down stop position 1 position 2 position 3 position 4 individual position When the alarm is activated the blind moves this p...

Page 20: ...tion communication object is updated After the bus voltage return forced position function set to the parametrized position Set the parameter to no forced position active The forced operation is deact...

Page 21: ...ING is deactivated Set the parameter to 1 When the telegram is received 1 HEATING operation is activated COOLING is deactivated Monitoring control valves yes no This parameter activate the thermostat...

Page 22: ...vel time This time is maximum one minute Valve limitation yes no The limitation of the control value limits the height of the control value The limitation is activated when a value is chosen which is...

Page 23: ...ons Thus initially the number of fan levels required for the connected devices can be defined The number of fan levels can be specified separately for each fan coil channel Controlling the fan levels...

Page 24: ...ime has elapsed 7 COMMUNICATION OBJECTS continued 7 10 Fan Coil parameter continued 7 10 2 A B1 Status Message parameter Enable communication object Status fan speed x 1 bit yes no The data format for...

Page 25: ...peed In s 0 65535 0 65535 This parameter defines the dwell time for a fan speed of the fan until it switches to the next higher or lower fan speed 0 no delay time for switching 7 COMMUNICATION OBJECTS...

Page 26: ...x Des 1 0x00 0 0x80 128 2 0x01 1 0x81 129 3 0x02 2 0x82 130 4 0x03 3 0x83 131 5 0x04 4 0x84 132 6 0x05 5 0x85 133 7 0x06 6 0x86 134 8 0x07 7 0x87 135 9 0x08 8 0x88 136 10 0x09 9 0x89 137 11 0x0A 10 0x...

Page 27: ...d operation 1 byte 0 255 DPT 5 001 brightness value 2 byte 32768 32767 DPT 7 001 signed value 2 byte 0 65535 DPT 8 001 unsigned value 4 byte float value DPT14 068 temperature 4 byte 0 4294967295 DPT12...

Page 28: ...or 4 104 Trigger reference movement Output A DTP 1 008 1 bit CW This object is triggered the reference movement If the telegram is received the blind is moved up or down end position Then the blind c...

Page 29: ...OMMUNICATION OBJECTS continued 7 17 Fan Object Description No Object name Name DTP Type Length Flags 95 Fan speed switch Fan DPT 5 010 1 byte CW This object is used to switch on fan speed via 1 byte o...

Reviews: