72 / 124
ECO Silver
Cooling thermostats (2)
RE 1225 S
RE 2025 S
RE 1050 S
Operating temperature, ACC *
°C
-25 – 200
-25 – 200
-50 – 200
Ambient temperature range
°C
5 – 40
Temperature stability
K
±0.02
Maximum storage temperature
°C
43
Cooler
Air
Air
Air
Cooling output at 20 °C
ambient temperature,
15 °C cooling water
temperature,
3 bar cooling water
pressure and Pump
Level 2
20 °C W
300
300
700
10 °C W
270
260
660
0 °C W
240
230
600
-10 °C W
180
150
520
-20 °C W
90
60
350
-25 °C W
40
30
---
-30 °C W
190
-40 °C W
100
-50 °C W
20
Bath volume
liters
9.3 – 12
14 – 20
8 – 10
Overall dimensions (W x D)
mm
200 x 200
300 x 350
200 x 200
Bath depth
mm
200
160
160
Usable depth
mm
180
140
140
Height to top edge of bath
mm
443
443
443
Overall dimensions (W x D)
mm
180 x 396
200 x 430
200 x 430
Overall height
mm
624
624
624
Weight
kg
30
37
34.6
Sound level (1 m)
dB(A)
50
50
52
Pump Connection Set
Plastic fittings Ø 13 mm
Mains connection
Heater rating / power consumption
230 V ±10 %; 50 Hz
kW
2.0 / 2.3
2.0 / 2.7
220 V ±10 %; 60 Hz
kW
1.9 / 2.2
1.9 / 2.6
115 V ±10 %; 60 Hz
kW
1.3 / 1.6
1.3 / 1.8
100 V ±10 %; 50/60 Hz
kW
1.0 / 1.3
1.0 / 1.7
*ACC range (Active Cooling Control) according to DIN 12876 is the working temperature range for operation with an
active chiller
Technical modifications reserved
Summary of Contents for ECO Silver E 10 S
Page 1: ...ECO Silver Operation manual ...
Page 2: ......
Page 4: ......
Page 78: ...78 124 ECO Silver 10 2019 i ...
Page 79: ...10 2019 i ECO Silver 79 124 ...
Page 80: ...80 124 ECO Silver 10 2019 i Appendix with settings ...
Page 111: ...10 2019 i ECO Silver 111 124 5 Click on Continue installation 6 Click on the key Finish ...
Page 113: ...10 2019 i ECO Silver 113 124 ...
Page 120: ...120 124 ECO Silver 10 2019 i Blank page ...
Page 121: ...10 2019 i ECO Silver 121 124 Blank page ...
Page 122: ...122 124 ECO Silver 10 2019 i ...
Page 125: ......
Page 126: ......
Page 127: ......