2: Installation
Figure 2-1. SLP Hardware View
Output
Power
Status LED
RS-232 Serial
(RJ45)
Outlet
Input
Current
LED
RJ12 Link
Connectors for Optional
Temperature/Humidity
Sensor
10/100Base-T
Ethernet
(RJ45)
Connectors for Optional
Temperature/Humidity
Sensor
RS-232 Serial
(RJ45)
)
AC Power
Inlet
Outlet
Input
Current
LED
10/100Base-T
Ethernet
(RJ45)
Output
Power
Status LED
RJ12 Link
AC Power
Inlet
Safety Precautions
This section contains important safety and regulatory information that should be
reviewed before installation. For input and output current ratings, see Power Ratings
in
Technical Specifications
.
Only for installation and use in a Service Access Location in accordance with the following
installation and use instructions.
This equipment is designed to be installed on a dedicated circuit.
Dedicated circuit must have circuit breaker or fuse protection.
This product has been designed without a master circuit breaker or fuse to avoid becoming
a single point of failure. It is the customer’s responsibility to provide adequate protection for
the dedicated power circuit. Protection of capacity equal to the current rating of the product
must be provided and must meet all applicable codes and regulations. In North America,
protection must have a 10,000A interrupt capacity.
The plug on the power supply cord shall be installed near the equipment and shall be easily
accessible.
Installation Orientation: SLPVxxxx-02 units are design to be installed in vertical orientation.
SecureLinx SLP Remote Power Manager
10