FMS Commissioning
O regulation
2
Operator controls and display
Mode switching
Selector switch (1) to status.
With channel key 3 in upward position, switch the display to O regulation.
2
O actual value and O target value are displayed whilst the switch is in the
2
2
Status position. If O regulation is deactivated, the figures are shown in
2
parentheses.
Push channel key 3 downward to return to VMS/FMS mode.
Note:
O actual and target values are only displayed if O regulation or
2
2
O display are activated by means of parameter 896.
2
In automatic operation, the display switches during regular operation to the
O regulation mode. During burner start-up and with the basic load,
2
VMS/FMS text mode is active - basic setting. However, switching the display
by means of channel key 3 is always possible. Nevertheless, the manually
preselected setting only remains in force until the next change-over into
"Regular operation” or "Basic load regulation”, and then returns
automatically to the basic setting.
In "O regulation” mode, and with the selector switch in the Status position,
2
pressing the Acceptance key calls up commentary texts (running texts)
relating to O regulation.
2
The selector switch position (2) O Regulation serves only for the input of
2
O target value curves.
2
55
O2 (I03.4 S03.1)
O2 (I03.4 S03.1)
POWER
OIL
GAS
ALARM
Channel-1
Channel-2
Channel-3
Channel-4
O regulation
2
deactivated
i
POWER
OIL
GAS
ALARM
Channel-1
Channel-2
Channel-3
Channel-4
O2 I03.4 S03.1
O2 I03.4 S03.1
O regulation
2
activated
ENTER
LAMTEC
LAMTEC
Feuerungs-Management-System FMS
PARAMETERISATION
O -CONTROL
2
SETTING
AUTOMATIC
CLEAR
MEMORY
MONITORING
DISPLAY
LOAD RATING
(CORR. INPUT)
SETPOINT
(running time-meter)
STATUS
(CORR. RANGE)
ACTUAL VALUE
FEEDBACK
SETPOINT
FEEDBACK
DIGITAL
INPUT
1
2
ENTER
LAMTEC
LAMTEC
Feuerungs-Management-System FMS
PARAMETERISATION
O -CONTROL
2
SETTING
AUTOMATIC
CLEAR
MEMORY
MONITORING
DISPLAY
LOAD RATING
(CORR. INPUT)
SETPOINT
(running time-meter)
STATUS
(CORR. RANGE)
ACTUAL VALUE
FEEDBACK
SETPOINT
FEEDBACK
DIGITAL
INPUT