151
Technical Data
Signal outputs
Monitor output:
4 … 20 mA signal, apparent ohmic resistance > 600
S
Correction inputs:
2, adjustable to 0 … 20 or 4 …20 mA
channel and effect adjustable via parameters
Digital outputs via
relay module R 16
(Contact material AgCdO, designed for 230 V AC switching voltage)
___________________________________________________________________
NOTE:
Only passive or non-reactive units may be connected to the outputs of
the R 0016 relay module. Any infeed of 230 V into the unit via terminals
82 - 92 in the event of a fault must be prevented.
___________________________________________________________________
230 V supply
All consumers connected to the R 16 relay module are supplied via this
terminal 81
terminal.
It is to have fuse protection provided by the customer in the form of a
max. 16A delayed action fuse.
Main gas 1
Contact for actuation of the gas line-side main gas valve
terminal 82
max. 2A, cos
max. 0.4
Main gas 2
Contact for actuation of the burner-side main gas valve
terminal 83
max. 2A, cos
max. 0.4
Oil
Contact for actuation of the two oil valves
terminal 84
max. 2A, cos
max. 0.4
Ignition valves
Contact for actuation of the ignition valve(s)
terminal 85
max. 2A, cos
max. 0.4
Ignition transformer
Contact for actuation of the ignition transformer
terminal 86
max. 2A, cos
max. 0.2
Fan (burner start)
Contact for actuation of the fan motor and all other components
terminal 89
that have to be activated at the start
max. 2A, cos
max. 0.8-1 (together with pre-ventilation signal)
Gas operation signal
Contact for signalling of the fuel selection. Not active in the off-state
terminal 90
max. 0.5A, cos
max. 0.8-1
Oil operation signal
Contact for signalling of the fuel selection. Always active in the off-state
terminal 88
max. 0.5A, cos
max. 0.8-1
Heated oil distribution
Contact for actuation of oil pre-heating. Active in oil operation from the
terminal 87
burner start to the main valve release
max. 2A, cos
max. 0.8-1
External pilot gas line
Contact for actuation of the shut-off valve of a more remote
terminal 91
pilot gas supply. Active from end of pre-ventilation to main valve release
max. 2A, cos
max. 0.4
If the contact is not needed for this purpose, the terminal must remain free
(e.g. in systems without pilot burner)
Pre-ventilation / Post-ventilation
Contact for signalling of the pre-ventilation or post-ventilation mode
terminal 92
max. 0.5 A, cos
max. 0.8-1 (together with fan)