27
3
System Operation
A10
Fault 211, 212, 213,
214, 215, 221, 222,
223, 224, 225
After switching from "Setting" to "Automatic" with burner running
TIP:
If switched from "Setting" to "Automatic" with the burner running, the FMS immediately as-
sumes its monitored operation. The value of the internal firing rate is set to the last known po-
sition of the compound in "Setting" and follows the external firing rate now. If this last
compound position cannot be properly determined (because a control element was moved
from the last accepted point by means of a switch before storing the curve, for example), the
value of the internal elements are too far removed from the set-point values, firing rate is
equated to that of the external firing rate. If the actual values of the control the fault "2
nd
mon-
itoring band“ is emitted.
The curve has nevertheless been properly stored.
Reset fault
A11
Fault 110
The program EPROM may be defective.
Request a new program EPROM from, LAMTEC, giving precise details of the order number
and contract number at the time, the agent's order and all software checksum for the FMS.
Please always return the defective EPROM (for address see back cover of this document).
A12
Fault 140, 107
EEPROM defective
The EEPROM of each processor contains important operating data, the parameters and the
curves.
When replacing this module, a basic setting must be provided before it is possible to do any-
thing else with the unit.
If the unit data are provided via PC interface it will be sufficient to feed these data into the new
EEPROM.
For details, see remote control software documentation.
If this is not possible, a pre-programmed EEPROM must be ordered from LAMTEC, quoting
the unit number and the software checksum.
This is essential in order to avoid any confusion.
For the address, see the back cover of the document.
A13
Fault 105
In checking the redundant curves an error was identified
If data were provided via PC interface:
Enter curve data again for the corresponding curve set
if this is not possible:
select appropriate curve set
Clear memory
Re-enter curve
A14
Fault 106
In checking the redundant parameters an error was identified.
Summary of Contents for FMS Series
Page 2: ......
Page 49: ...48 4 Appendix Gas operation without pilot burner with leakage test...
Page 51: ...50 4 Appendix 4 1 2 Oil Operation Oil operation with pilot burner and flame monitor...
Page 52: ...51 4 Appendix Oil operation without pilot burner...
Page 54: ...53 4 Appendix 4 2 Connection Diagram Relay Modules 4 2 1 Connection Diagram Type 660 R 0016...
Page 73: ......