52
4
Appendix
Caption to the process sequence charts
* if output regulator in the unit is activated, the signal is linked with the internal burner-start of
this regulator.
** If the re-circulation signal is absent, re-circulation valves remain closed or run closed
(xpect at pre-ventilation).
*** Signal on terminal 1 clears the time t3, t4, at the end of t1.
**** For determination of the total safety times, according to the standards, you may have to
add the reaction time of the flame monitor to the settings of the FMS (typ. 1 sec.).
any conditiong
t1
air pressure monitor min. scan
any
t2
time for pressure build-up in the gas test line (only
available if leakage test is activated)
2 sec.
t3
running time servo drive
t4
delay re-circulation dumper
0 - t5
t5
aeration time
30 - 999 sec. adjustable
t6
pre-ignition time
2 - 40 sec.****
t7
1
st
safety time
4 sec.
t8
stabilisation time
3 - 10 sec. adjustable
t9
2
nd
safety time
4 sec.****
t10
operating phase
any
t11
control mode
any
t13
post-ventilation time
0-999 sec. adjustable
t14
control elements at base load
t15
afterburning time
0 - 30 sec. adjustable
t16
flame extinguishing check
5 sec.
t17
leakage test gas valve 2
30 sec.
Summary of Contents for FMS Series
Page 2: ......
Page 49: ...48 4 Appendix Gas operation without pilot burner with leakage test...
Page 51: ...50 4 Appendix 4 1 2 Oil Operation Oil operation with pilot burner and flame monitor...
Page 52: ...51 4 Appendix Oil operation without pilot burner...
Page 54: ...53 4 Appendix 4 2 Connection Diagram Relay Modules 4 2 1 Connection Diagram Type 660 R 0016...
Page 73: ......