23
3
System Operation
627
General safety chain missing
700
Pre-ventilating signal present, without signal on terminal 2.
G2,G5
701
Flame signal present, without signal on terminal 2.
G2
702
Flame signal appears during pre-ventilating.
G2,G5
703
Flame signal goes out even though signal on terminal 2 is still present.
G2
711
Illegal operating mode change.
H6
712
713
Incorrect signal combination in operating mode AU
H6
714
Incorrect signal combination in operating mode BE
H6
715
Incorrect signal combination in operating mode VO
H6
716
Incorrect signal combination in operating mode ZP
H6
717
Incorrect signal combination in operating mode ZU
H6
718
719
Fuel valves open too long without flame
H6
720
Ignition transformer switched on too long
H6
721
Ignition valve open too long
H6
722
Fuel valves open in maintenance mode
H6
723
Ignition process taking too long
H6
724
Gas valves open when burning oil
H6
725
Oil valves open when burning gas
H6
726
Main gas 2 open without main gas 1
H6
727
Main gas 1 illegally open
H6
728
Main gas valves and ignition valve open too long
H6
729
Ignition process taking too long (without pilot burner)
H6
730
Maintenance mode without pilot burner
H6
731
Ignition valve open without pilot burner
H6
732
Incorrect signal combination during operation
H6
733
Incorrect signal combination after operation
H6
734
Pre-ventilating time not complied with
H6, H8
735
Fuel safety chain missing
H6
736
Leak check: both gas valves open
H6
737
Leak check: main gas 2 delayed too long when switching off
H6
738
Leak check: main gas 2 missing
H6
739
Leak check: main gas 2 open too long
H6
740
Leak check: main gas 1 leaking
H6
741
Leak check: main gas 1 open too long
H6
742
Leak check: main gas 2 leaking
H6
743
Flame monitoring: flame after-burn too long
H6
744
Flame monitoring: flame on again
H6
745
Program check time exceeded
746
Solenoid valve switch-off faulty
H6
747
Leak check: ventilating into boiler not allowed
H6
Aids FMS
Aids ETA
Summary of Contents for FMS Series
Page 2: ......
Page 49: ...48 4 Appendix Gas operation without pilot burner with leakage test...
Page 51: ...50 4 Appendix 4 1 2 Oil Operation Oil operation with pilot burner and flame monitor...
Page 52: ...51 4 Appendix Oil operation without pilot burner...
Page 54: ...53 4 Appendix 4 2 Connection Diagram Relay Modules 4 2 1 Connection Diagram Type 660 R 0016...
Page 73: ......