24
3
System
Operation
750
Shut-down on faults via bus.
751**
No data transfer via the bus (time-out).
759
Operating mode ADJUSTMENT did exceed the time limit of 24 hrs
760
Change of curve selection during setting not allowed
G3
761
Change of curve lasts too long
763
Different curve selection between the processors
764
CO-Controller, internal fault no. -
765
Parameter setting error: The channel for solo-fuel is not to determine.
766
The limited load (maximum load without additional-fuel) does not exist in the
priority curves.
767
One parameter of the interpolation type for the non-fuels is invalid.
768
The curve-set-variable for the assigned air channel (1-priority 2-additional
curve) is invalid.
769
Ignition while mixed fuel operation or burner-start with solo-fuel-A
770
Fill-Time for fuel-A to long
791**
Bus master is in stop.
792**
Bus data length incorrectly configured.
793**
Bus master is decoupled.
800
Error in parameters, for parameter no.:
A7, A9,
A14
888
Fault block activated!
889
Remote-fault-reset happens within a too short distance
900
Error in self-test sequencer.
A7
901
Terminal 10 +24 Volt switch-off faulty.
A7, A21,
A22
902
Error in overvoltage self-test.
A7
903
Error in optical coupler self-test.
A7,G7
904*
Error in reference of load
A7,A21
905*
Error in reference element of main processor
A7,A21
906*
Error in reference element of monitoring processor
A7,A21
907
Curve set adjustment via Lamtec System Bus, self-test recognizes fault
911*
Error in reference, channel: 1
A7,A21
912*
Error in reference, channel: 2
A7,A21
913*
Error in reference, channel: 3
A7,A21
914*
Error in reference, channel: 4
A7,A21
915*
Error in reference, channel: 5
A7,A21
921
Relay driver self-test: output terminal 11 or 66 (ETAMATIC) faulty.
A19,A7
922
Relay driver self-test: output terminal 16 or 65 (ETAMATIC) faulty.
A19,A7
923
Relay driver self-test: output terminal 43 or 68 (ETAMATIC) faulty.
A19,A7
924
Relay driver self-test: output terminal 67 faulty.
A19,A7
925
Relay driver self-test: output terminal 45 faulty.
A19,A7
926
Relay driver self-test: output terminal 68 or 61 (ETAMATIC) faulty.
A19,A7
927
Relay driver self-test: output terminal 36 (ETAMATIC K202) faulty.
A19,A7
Aids FMS
Aids ETA
Summary of Contents for FMS Series
Page 2: ......
Page 49: ...48 4 Appendix Gas operation without pilot burner with leakage test...
Page 51: ...50 4 Appendix 4 1 2 Oil Operation Oil operation with pilot burner and flame monitor...
Page 52: ...51 4 Appendix Oil operation without pilot burner...
Page 54: ...53 4 Appendix 4 2 Connection Diagram Relay Modules 4 2 1 Connection Diagram Type 660 R 0016...
Page 73: ......