34
3
System
Operation
D6
Load rating does not attain the highest value indicated
If the load transducer is in the maximum position but does not emit the highest possible value.
Make sure that this position of the load transducer is the highest load rating position that oc-
curs in operation.
D7
Fault 320
Load input is not correctly connected.
In the case of load due to current default:
Current is less than 4 mA, poles possible reversed
Check wiring
Check input current
D11
Fault 372
The two load ratings for main and monitoring processor are compared with one another.
Change processor card.