14
3
System
Operation
Calling up
running time meter
TIP:
The sum of the curve set 1 running hours and curve set 2 running hours does not necessarily
give the running hours value displayed in total. The total counter relates to the FMS running
hours. It runs as soon as the unit is connected to a voltage (this also provides the basis for the
fault history).
The single running time meters relate to the burner running hours. These run as soon as the
burner is in operation with the respective curve set (flame signal to the FMS).
3.4
Messages / Faults
TIP:
If the processor detects a fault, it runs the outputs in the programmed direction, of FMS fault
e.g. air on, fuel off, re-circulation closed The fuel solenoid valves close. The fault signal relay
pulls on with a few seconds delay. Automatic restarting may be possible, depending on the
nature of the fault
Reading the faults
Red fault LED lights up
Selector switch to "Status”
- Fault code is displayed
Note code
Press Enter
- Plain text message appears on display incl. running time meter reading up to the time of the
fault
Selector switch on "Load rating“
- Load rating at the time of the fault is displayed (externally and internally)
Note load ratings
Fault reset
Selector switch to "Status”
Left-hand switch up
- the fault is cleared unless the cause is still directly present.
Selector switch (1) to set-point
Press "Enter" (3) and keep pressed
–
a moving text appears giving the following data:
–
total running hours
–
running hours on curve set 1
–
starts on curve set 1
–
running hours on curve set 2
–
starts on curve set 2
Where the 4 curve set or 8 curve set option is used the running hours and
starts on the additional curve sets are also displayed.
Summary of Contents for FMS Series
Page 2: ......
Page 49: ...48 4 Appendix Gas operation without pilot burner with leakage test...
Page 51: ...50 4 Appendix 4 1 2 Oil Operation Oil operation with pilot burner and flame monitor...
Page 52: ...51 4 Appendix Oil operation without pilot burner...
Page 54: ...53 4 Appendix 4 2 Connection Diagram Relay Modules 4 2 1 Connection Diagram Type 660 R 0016...
Page 73: ......