10 Correcting Faults
10
Correcting Faults
10.1
Fault Finding and Troubleshooting
10.1.1
Commissioning
Cable types and cross sections to be used
Shielded cables e.g. LiYCY
Cross-section:> = 0.5 mm
2
, 20 AWG
NOTICE
The maximum length of the FSB is 80 m (both directions); for length> 80 m, intermediate am-
plifiers (repeaters) must be used.
Problem
Possible cause
Remedy
No Bus communica-
tion via the main con-
necting cable
Bus is not correctly termi-
nated.
F300K with user interface
•
Use the User Interface to switch the terminating
resistor on.
F300K
•
Use a connecting cable that is as short as possible.
•
Termination: Connect a 120
terminating resistor to
the last device connected to the bus.
•
Switch the terminating resistor on again in the
F300K.
External User Interface
•
Switch on the terminating resistor with the external
User Interface (
7.6.2 Parameterising the User Inter-
USB/FSB module
•
Add the terminating resistor.
Installation, commissioning, maintenance
•
Note the document "supply and engineering guide".
Fig. 10-1 CAN bus termination
The error LED
flashes constantly
although the error
has been eliminated
and/or an error can-
not be read out.
A serious error has occurred
resulting in the prevention of
an automatic RESET.
•
Reset the hardware by interrupting the supply volt-
age for approximately 10 seconds.
•
Read the error out after switching the device on
again.
•
If the error occurs again, contact the manufacturer.