107
14
Appendix
1
The product must not be operated outside the specified range. If it is, any guarantees with regard to safety-related functions lose
their validity.
Mains frequency:
47 ... 63 Hz
Input parameters
Output parameters
Output direct voltage:
24 VDC, adjustment range 21.6 V - 26.4 V
Maximum current drain:
FN30-00 IP20 0.9 A
FN30-10 IP66 0,45 A
Short-circuit resistant:
Constant current limiting
Connection cross-section
Flexible:
0.5 … 2.5 mm
2
/20 AWG ... 12 AWG
Climatic range
Protection class:
1
- FN30-00 IP20 - IP40 must be achieved as a minimum fol-
lowing installation
- FN30-10 IP66
Protection class:
Isolation class II, EN 60950-1, UL 60950-1
Operating temperature range
Ambient temperature:
1
-20 … + 60 °C/-4 ... +140 °F
Humidity:
FN30 IP20
relative humidity of 20 ... 90 % RH non-con-
densing
FN30 IP66
relative humidity of 0 ... 95 % RH non-condens-
ing
Storage/transport conditions
Storage location:
Enclosed spaces
Air temperature:
1
- 40 … + 85 °C/-40 ... +185 °F
Humidity:
Relative humidity of 10 ... 95 % RH non-condensing
Weight:
FN30-00
0.27 kg
FN30-10
1.80 kg