3
When the burner motor is started a pre-
ventilation period of 30 seconds begins
during which the ignition transformer is also
activated. When the pre-ventilation and
pre-ignition phase has been completed, the
selected fuel valve opens and the fuel starts
to flow with formation of the flame. If the
flame does not appear 3 seconds after ope-
ning the fuel valve, the burner locks. If the
flame accidentally goes out during normal
operation, the burner locks completely. The
burner is turned on again by pressing the
lock reset button (7).
t
3
– 30 sec. pre-ventilation and pre-ignition
t
– 3 sec. MAX safety time
OPERATING CYCLE
Fig-7
EV gas o oil
EV gas o oil
The power supply line must be connected to the burner by means of a 0A main switch protected
with 3A fuse valves.
The connection cables must have a cross-section of not less than mm
and 000V insulation. For
connection of the line and auxiliary devices follow the wiring diagram.
The burner must be connected to earth in accordance with the EMPI regulations in force.
IGNITION
NO IGNITION
WIRING DIAGRAM