51
Gas type
L.C.V.
kcal/h
8.550
29.330
22.360
Diaphragm (H)
XILO T 24 MS
MS
Ø
M
Ø
Burner
jets
Ø mm.
1,25
0,77
0,77
Delivery
Jets pressure mbar
XILO T 24 M
NOx
Class
1
1
1
M MS
3
-
6,4
6,4
-
6,2
6,2
3
3
m
3
/h
max.
min.
max.
min.
3,04
0,89
1,16
12,5
26,8
34,5
2,2
6,5
8,5
12,5
25,6
33
3
6,3
8,6
OPERATION WITH DIFFERENT TYPES OF GAS
CONVERSION FROM NATURAL GAS TO LIQUID GAS
The boiler is factory-set for
G20
(Natural Gas) or
G30/G31
(LPG) operation, as mentioned on the Technical
Nameplate and on the apparatus packaging. In the event the heater shall be operated using a different gas
from that conceived by factory setting, a special kit has to be installed, which is to be ordered separately.
To perform conversion, act as follows:
- Remove the cover and open the tight chamber (for model MS)
-
Unscrew the fastening screws (1) and remove the burner (2) (fig. 1)
-
Replace the burner nozzles (3) with those supplied with the transformation kit, making sure that the
relevant diameter corresponds to that reported in the table shown below. Insert the sealing rings
-
Reassemble the burner
-
Close the tight chamber checking proper positioning of seal gaskets (for model MS)
Then act as follows:
For transformation from
G20
(Natural Gas) to
G30/G31
(LPG):
- Insert the gas diaphram (fig. 2 )
- Move jumper JP1 to ON position (fig. 3)
- Disconnect the pressure regulator by screwing tight the nut (H) (page 48) and adjust minimum pressure to the
value reported in the table shown below by acting on the screw (I) (page 48)
- If necessary, adjust trimmers RLA and R.MAX according to the system features
- Seal the regulator by applying the cover ( G )
For transformation from
G30/G31
(LPG) to
G20
(Natural Gas):
- Remove the gas diaphram
- Move jumper JP1 to OFF position (fig. 3)
- Regulate the pressure (maximum and
minimum values) of the burner according
to the values reported in the table shown
below, by acting on the nut (H) and on the
screw (I) respectively, as described in
paragraph ‘ADJUSTMENTS’ (page 48)
-
If necessary, adjust trimmers RLA and
R.MAX according to the system features
-
To confirm transformation, apply the
adhesive plate supplied with the transfor-
mation KIT on the Technical Nameplate
reporting the information featuring the gas,
and according to the factory-setting.
Ø
Gas Valve
Gas Diaphragm
Gasket
fig. 2
fig. 1
fig. 3
Legend:
G30/G31
LPG
G20
Natural Gas
JP1
Off
On
G20-20mbar
(Natural Gas)
G30-28/30mbar
(LPG)
G31-37mbar
(LPG)