Pilot burner assembly
1
Combustion chamber door
2
Inspection door
3
Pilot burner
4
Ignition electrode
5
Detection electrode
6
Pilot nozzle
7
High voltage cable
8
Gas supply pipe
4.4 Troubleshooting
Table. 1 - Fault list
fig. 10 - Pilot burner
3
3 ÷ 4 mm
5
4
8
Fault
Cause
Cure
After several lighting attempts, the elec-
tronic controller shuts down the boiler
Pilot burner nozzle dirty
Clean the nozzle with compressed air
Air in gas pipes
Check the regular gas flow to the boiler
and that the air has been eliminated
from the pipes
No discharge between elec-
trodes
Make sure the electrodes are correctly
positioned, integral, free of any depos-
its and that the spark is regular (see
fig. 10)
Check the electrical connections at the
ignition and ionisation electrodes
Faulty gas valve
Replace the valve
The boiler does not start
Electric mains trouble
Make sure the boiler is connected to
the mains rated voltage and to an effi-
cient earth connection
Electric mains trouble
Make sure the LINE and NEUTRAL are
not inverted and that the earth contacts
are efficient
Wiring fault
Check the connections to the electronic
flame controller
No gas
Check the inlet gas pressure and any
open gas pressure switches
Fume thermostat activation
Reset the fume thermostat
Room thermostat open
Make sure the room thermostat is
closed in call
The burner burns poorly:
flames too high, too low or too yellow
Gas pressure too low
Check the gas supply pressure
Gas nozzles dirty or wrong
Check the nozzles and clean if neces-
sary
Poor ventilation
Make sure the ventilation in the room
where the unit is located is sufficient for
proper combustion
Smell of unburnt gas
Boiler dirty
Check and clean the boiler shell
Poor flue draught
Check the efficiency of the flue draught
Incorrect excess flame
adjustment
Make sure the gas consumption is not
excessive (gas pressure switch nozzles
or diameter)
The boiler works but the temperature
fails to increase
Incorrect control thermostat
setting
Check correct operation of the control
thermostat
Incorrect flame adjustment
Make sure gas consumption is not less
than that provided for
Boiler dirty
Make sure the boiler is perfectly clean
Boiler inefficient
Make sure the boiler is adequate for the
system
No water circulation in the
system
Make sure the heating pump is not
blocked and that the plumbing circuit is
not dirty
Temperature of water towards the sys-
tem too high
Incorrect thermostat setting
Check operation of the control thermo-
stat
Incorrect thermostat posi-
tioning
Check the bulb position
Explosion at burner
Ignition delays
Excess gas
Check the main burner gas pressure
Boiler dirty
Check and clean the boiler shell
Burner dirty
Check and clean the burner
Wrong nozzles
Check the nozzles
The boiler produces condensation
water
Incorrect thermostat setting
Make sure the boiler is not operating at
too low temperatures (below 40°C)
Insufficient gas consumption
Make sure gas consumption is regular
The boiler shuts down for no apparent
reason
Fume thermostat activation
Check for any obstructions in the flue
and manually reset the fume thermostat
Summary of Contents for GASTER N 56 AW
Page 10: ......
Page 19: ......
Page 28: ......
Page 49: ...49 RU cod 3540S420 05 2010 Rev 00 1 2 3 4 5 6 7 8 4 4 1 fig 10 3 3 4 mm 5 4 8 10 40 C...
Page 51: ...51 RU cod 3540S420 05 2010 Rev 00 5 5 14 24 32 44 49 63 72 82 83 92 98 129 159 160 A...
Page 52: ...52 RU cod 3540S420 05 2010 Rev 00 15 24 32 44 49 63 72 82 83 92 98 129 159 160 A...
Page 63: ......