23
Equalize Timer Settings
The Equalize Timer Settings submenu provides access to the change the Equalize Timer Mode, and Equalize Timer
Hours.
Equalize Timer Mode
The Equalize timer mode determines when the charger will go into an Equalize charging cycle. The timer modes
are “Auto EQ OFF”, “7 Day Auto EQ”, “14 Day Auto EQ”, “30 Day Auto EQ”, and “Auto EQ on LV”. The default
setting for the Equalize timer mode is Auto EQ OFF. The Equalize Timer Modes are discussed in further detail in
Section 3.3.1.
Equalize Timer Hours
The Equalize timer hours setting changes the amount of time that the charger remains in the Equalize charging
cycle once activated. When an Equalize cycle is started the charger will remain in Equalize Mode until the time
selected by this setting has passed. The Equalize timer can be set between 1-144 hours, by default the Equalize
timer is set for 8 hours. The battery manufacturer recommendations should be followed.
Advanced Alarm Settings
The Advanced Alarm settings allow the user to access and modify additional parameters of the charger, such as
the Alarm Delays and Alarm Operation.
Alarm Delays
The Alarm Delays setting allows the user to determine the time delay between the alarm condition and alarm
indication. If an alarm condition returns to normal before the delay time, the alarm will not indicate. The delay
can be changed for Overload Alarm, End of Discharge Alarm, Ground Detection Alarm, AC Alarm, Low Current
Alarm, Low Voltage Alarm, High Voltage Alarm, and High Voltage Shutdown Alarm. The delay for all alarms is
adjustable between 1-300 seconds.
Alarm Operation
The Alarm Operation setting defines if the alarms relays latch. The relay latch setting can be changed for Summary
Alarm, AC Power Fail Alarm, Low Current Alarm, Low Voltage Alarm, High Voltage Alarm, Positive Ground Alarm,
and Negative Ground Alarm. If any alarm contacts are set to latch, the alarm will not clear until the ALARM RESET
button is pressed, even if the alarm condition returns to normal.
By default, no alarms are set as latching, except for High Voltage Shutdown (HVSD). All other alarms will clear
after the condition returns to normal.
NOTE:
The HVSD alarm latches by default and cannot be changed.
< Equalize >
Timer Mode
< EQ Timer Mode
Auto EQ OFF
< Equalize >
Timer Hours
< EQ Timer
8 Hours
< Alarm >
Delays
< OL Alarm Delay
5 Seconds
< End of Dis.
5 Seconds
< GND Det Alarm
Delay 5 Seconds
< AC Alarm Delay
5 Seconds
< LC Alarm Delay
5 Seconds
< LV Alarm Delay
5 Seconds
< HV Alarm Delay
5 Seconds
< HVSD Alarm Dly
20 Seconds