18
3
Operation
3.1
Starting the TPSD2
All equipment is shipped from the factory fully checked and adjusted based on the customer order. Do not make
any adjustments unless the equipment has been powered-up and the settings have been determined to be
incorrect. Check with battery manufacturer for recommended settings.
Factory Settings
The adjustable factory settings of the TPSD2 are based on the customer order, unless otherwise specified. All
chargers are set at the factory with the following settings:
Parameter
Lead Acid
VRLA
Nickel Cadmium
Delay (sec.)
Float Voltage
2.17 V/C
2.25 V/C
1.40 V/C
Equalize Voltage
2.33 V/C
2.27 V/C
1.55 V/C
Low DC Voltage
1.98 V/C
1.20 V/C
5
Low DC Voltage Reset
5% of the Low DC Voltage threshold
Low DC Current
1% of shunt size
5
Low DC Current Reset
Dependent on output current rating
Overload
Dependent on output current rating
5
Overload Reset
5% of the Overload threshold
Current Limit
115% of nominal output current
5
High DC Voltage
2.45 V/C
1.61 V/C
5
High DC Voltage Reset
5% of the High DC Voltage threshold
High Voltage Shutdown
2.50 V/C
1.65 V/C
20
Battery End of Discharge
1.75 V/C
1.10 V/C
5
End of Discharge Reset
5% of the End of Discharge threshold
Equalize Timer Mode
Automatic Equalize Off (Mode P0)
Equalize Time
8 Hours
Table 9 – Factory Default Values
NOTE:
V/C – Volts per Cell, LA – Lead Acid, VRLA – Valve Regulated Lead Acid, NC – Nickel Cadmium
3.1.1 Checking the Installation
Before attempting to start up the TPSD2, check and verify that all connections are correct. Check that all
terminations and contacts are tightened securely. Check for any loose connection or unsecured components in
the charger. Check that the transformer is set for the correct input voltage and that the input frequency matches
the nameplate or the charger. Check that the battery/load voltage matches the DC output voltage on the
nameplate of the charger. Verify AC feeder breaker matches charger input protection rating.