Explanation of the operating elements  

Operation

 

 

Starting up 

Starting up 

After the device has been properly installed, switch on 
the power supply. 
The software number for your device and then the 
index of your software briefly appears in the display. 
Then the readout appears in accordance with the 
position of the selection switch. 

The controller is now operational => "Run" 

Modifying set values 

Rotate the selection switch to the corresponding set 
value 

The display shows the currently set value. 

Press the OK button. 

The value now starts to flash and can now be 
changed by means of the rotary knob (only if a 
modification is possible and permissible). 

By pressing the OK button once more, the value is 
stored in the device. 

Rotate the selection switch to RUN Automatic mode 
=> the mode is activated after 2 seconds. 

 

List of the User Set Values 

Designation 

Area 

Factory  IV 

Run => Normal mode  
Display level with 

 

rotary knob 

- - 

 

 

°C

D

 (Max T-Boiler= 95°C) =  

with fixed value => Flow /Return 
flow set temperature*) 
Cascade: Max T-Boiler 

20°C - 110°C 

 
 

Display only 

40°C 

 

°C

 

F

 = during hot water 

operation:HW set temperature 

No function 

-- 

 

v

 

b

 = with return flow 

temperature increase via Mixer 
and Mod: Mixer dynamics 
With modulation in cascade: 
Activation time of the air damper 

--, 01K – 25K 

 
 

0s – 60s 

-- 

(12K) 

 

20s 

 

°C

 

D

 = in the case of return 

flow temperature increase: min. 
return flow temperature 

10°C - 80°C 

30°C 

 

H

 1/2/11/Mod = Heat generator 

stages 

1/2/2A/11/m 2 

 

BUS ID = Bus identification / 
Heat generator number 

-01, 01 – 08 

11-88 

01 

 

j

1  Service 1 / Emerg-Mode 

+ Prog-button = Relay Test 
01-05 (see display symbols) 

00 – 05 

00 = OFF 

01-05 = ON 

00 

 

j

2 Service 2 (see Selection 

switch)

 

- - 

 

 

i

 Standby (OFF) 

- - 

 

 

Summary of Contents for Basic 0201 R V1

Page 1: ...Lago Basic 0201 R V1 Heating module Operating and Installation Instructions Please observe the safety instructions and read through this manual carefully before commissioning the equipment...

Page 2: ...null and void Important text passages Important information is highlighted with an exclamation mark E This attention symbol is used to point out dangers in this manual Installation Information on ins...

Page 3: ...ar side 8 Functions 8 Operation in the cascade 8 Modulation in the cascade 8 Operation of a single heat generator 9 Stand alone 9 Single HS with Manager via CAN BUS 9 Modulation via air damper 9 Frost...

Page 4: ...in cascade Air damper activation time s C D in the case of return flow temperature increase min return flow temperature H 1 2 11 Mod heat generator stages 1 single stage 2 two stage 11 2HS m modulati...

Page 5: ...ls below the display with return flow temperature increase With return flow temperature increase sensor and mixer dynamic F K Mixer OPENS arrow points upward d Mixer CLOSES arrow points downward With...

Page 6: ...the device Rotate the selection switch to RUN Automatic mode the mode is activated after 2 seconds List of the User Set Values Designation Area Factory IV Run Normal mode Display level with rotary kn...

Page 7: ...re increase pump The setting 12 12K deviation 100 ID cannot be used for most mixer motors Small values cause the mixer to adjust quickly and can lead to oscillation Modulation H 1 2 11 Mod m Stand alo...

Page 8: ...rs The controller can be used to actuate any of the following configurations A single stage heat generator with associated boiler pump and return flow temperature increase via pump or mixer 1 2 11 Mod...

Page 9: ...temperature at Sensor T BOILER to the value T BOILER DES preset in the Manager Modulation via air damper The initial damper adjustment occurs with a delay of approx 3 minutes after a burner start Whil...

Page 10: ...blocking of generator Return flow temperature Minimum return flow temperature or burner OFF and after run time of pump has elapsed EEPROM check Every 10 minutes a check is conducted automatically in...

Page 11: ...General information Assembly Dismantling 11 Installation Installation Assembly Dismantling 3 x 0 5 a b c...

Page 12: ...or an operating voltage of 230 V AC at 50 Hz The burner contact is a floating contact and must always be connected in series with the mechanical boiler thermostat 230V Relay switching capacity 2 2 A 2...

Page 13: ...troller in cascade operation A Heat generator with temperature sensor KF and switch input T1 T2 B HS pump possibly in heating circuit flow C Return flow sensor VF D Mixer Temperature increase of retur...

Page 14: ...ion location In the immersed pipe of the hot water cylinder tank generally on the front face of the tank Installation Slide the sensor as far as possible into the immersed pipe The immersed sleeve mus...

Page 15: ...458 1607 100 C 339 1713 110 C 255 1823 120 C 194 1936 Errors When there is an error the corresponding error number flashes Resetting error number 81 Switch mains voltage Off and On again Error no Erro...

Page 16: ...6 3 A Type of protection complying with DIN EN 60529 IP 40 Protection class complying with DIN EN 60730 Totally insulated Permitted ambient temperature during operation 0 to 50 C Permitted ambient te...

Reviews: