General information
Assembly / Dismantling
15
Sensor values / characteristic curve
Temperature 5Kohm NTC
1Kohm PTC
-60°C
698961
Ω
470
Ω
-50°C
333908
Ω
520
Ω
-40°C
167835
Ω
573
Ω
-30°C
88340
Ω
630
Ω
-20°C
48487
Ω
690
Ω
-10°C
27648
Ω
755
Ω
0°C
16325
Ω
823
Ω
10°C
9952
Ω
895
Ω
20°C
6247
Ω
971
Ω
25°C
5000
Ω
1010
Ω
30°C
4028
Ω
1050
Ω
40°C
2662
Ω
1134
Ω
50°C
1801
Ω
1221
Ω
60°C
1244
Ω
1312
Ω
70°C
876
Ω
1406
Ω
80°C
628
Ω
1505
Ω
90°C
458
Ω
1607
Ω
100°C
339
Ω
1713
Ω
110°C
255
Ω
1823
Ω
120°C
194
Ω
1936
Ω
Errors
When there is an error, the corresponding error number
flashes.
Resetting error number 81:
Switch mains voltage Off and On again.
Error no. Error description
Communication error
E 91
Bus ID used. The set bus ID is already in use
by another device.
Internal error
E 81
EEPROM error. The invalid value has been
replaced with the default value
E
Check parameter values!
Sensor defective (break/short circuit)
E 70
Flow sensor
E 75
Outdoor sensor
E 76
Storage tank sensor
E 77
Boiler sensor
E 80
Room sensor