Foreman Ductable Dual Fuel Indirect-Fired Heater
www.lbwhite.com
Owner’s Manual • Foreman
12
IN EXISTING CHIMNEY
DIRECTLY TO OUTSIDE
Inside Structure
Outside Structure
To prevent recirculation of
fl
ue gas from the exhaust
outlet to the heater air inlet, an exhaust stack of
5ft./1.25meter minimum is required to be installed
onto the exhaust outlet. To protect against water
entry when the heater is installed outdoors, a rain
cap is necessary.
Optional accessory chimney (Part #30161) and rain
cap (Part #30162) may be purchased through the
L. B. White Co.
WARNING
Asphyxiation Hazard
■
When installing indoors, the heater’s exhaust
must be vented to the outside.
■
Failure to comply can result in asphyxiation
due to lack of adequate air supply or carbon
monoxide poisoning.
■
Carbon monoxide poisoning can lead to seri-
ous injury or death.
1
Rain Cap
Chimney
Exhaust Outlet
1) Anti-wind device, optional accessory
A. Minimal 3 Ft.
2) Horizontal crossing with minimal upside angle pitch of 5°
B. Minimal 3 ft.
3) Chimney 8 in. x 8 in. of minimal inside measure
C. Shortest
4) Chimney
anti-explosion
fl
ap door
D. The same or bigger than the
5) External seating wall
heaters stack outlet diameter.
E. Minimal 3 ft.
Note:
The above information is a recommendation only.
Have you installation checked by a local authority.