Oval 80 and Sentinel Radiant Tube Brood Heaters
www.lbwhite.com
Owner’s Manual • Oval 80 and Sentinel
16
Refer to the brood heater’s burner box hinged access
panel, or refer to Start-up instructions in this manual to
determine if your brood heater has a single or two stage
gas control.
When connecting a thermostat or building controller to the
burner box, route the wiring through the watertight con-
nector near the power cord after removing the connector’s
plug. See Fig.14. If the connector does not completley
seal around the wiring after tightening, apply silicone at
the wire entry of the connector.
All interconnecting thermostat wiring must
be at least 18 gauge to prevent voltage
drop. Ensure the terminal marked W on the
ignition control receives 24 VAC from the
thermostat or building controller.
A. Brood heaters with Single Stage Gas
Control Valve
1. Connecting series tap thermostat kit.
-- Connect power cord of brood heater to female side of
thermostat cord set.
-- Plug the male side of cord set into an approved exten-
sion cord or to wall outlet.
Brood Heater Controls
WARNING
Electrical Shock Hazard
■
Disconnect the brood heater’s electrical supply
before interconnecting the temperature control.
■
Failure to disconnect the electrical supply will
result in electrical shock.
■
Electrical shock will cause severe injury or
death.
FIG. 14
FIG. 15
TIGHTEN CONNECTOR SECURELY
AFTER INSTALLING THERMOSTAT CORD
2. Wiring Thermostat
(See Fig. 15)
-- Remove wire nut at yellow and orange wire.
-- Connect wiring of thermostat as shown or refer to
electrical diagram on heater
3. Building Controller Connections
(See Fig. 16)
-- Remove wire nut from yellow and orange wires.
-- Connect controller contacts as shown.
FIG. 16