Oval 80 and Sentinel Radiant Tube Brood Heaters
Owner’s Manual • Oval 80 and Sentinel
15
REGULATOR
NIPPLE
VALVE, MANUAL
SHUT-OFF
GAS HOSE
ADAPTER
SEDIMENT TRAP
TO CONTROL
VALVE INLET
REGULATOR VENT
GAS FLO
W
SENTINEL BROOD HEATERS: Assemble the strips
and insert into last tube, see Fig. 10. Edge of strip is
fl
ush with end of tube.
OVAL 80 BROOD HEATERS: Both strips
are factory installed into the oval tube.
At installation, ensure strips are snugly
fi t into oval tube and do not extend past
end of tube.
Assemble the tee, nipple, and cap to the nipple at
the gas inlet of brood heater. See Fig. 12. Tighten
securely. The sediment trap assembly must always be
mounted in a vertical position. Check all connections
for gas leaks using approved gas leak detectors.
1. Assemble the components together. See Fig. 13.
This view shows general assembly of the compo-
nents. The regulator must always be mounted so its
vent, regardless of location on the regulator, is al-
ways pointed downward. Ensure hose is positioned
away from the heater.
2. Tighten all connections securely and check
for gas leaks
REGARDLESS OF TUBE DESIGN:
-- FORM THE VENT’S STRAP AROUND END OF
LAST TUBE.
-- DO NOT WRAP THE VENT STRAP DIRECTLY
ONTO TUBE.
-- PUSH THE STRAP STOPS FIRMLY AGAINST EDGE
OF TUBE. SEE FIG. 11.
-- TIGHTEN THE STRAP SCREW SECURELY.
-- ENSURE FLAPPER DOES NOT BIND
Air Turbulation Strips
& Vent
Sediment Trap Assembly
Manual Shut-off
Valve, Hose &
Regulator
FIG. 10
FIG. 12
FIG. 13
FIG. 11
VENT FLAPPER MUST LIFT
AND DROP FREELY
STRAP STOPS
NIPPLE
TEE
NIPPLE
CAP
OUTLET END
TO GAS CONTROL VALVE INLET
INSERT STRIP ASSEMBLY
INTO LAST 3.05M OF TUBE