6.3 Connecting the device to the electrical supply
The device is equipped with a standard connection cable. Before commissioning, the plug of
the connection cable has to be plugged into the standard socket 16 A, 230 V ac.
6.4 Commissioning of the device
After connecting the electrical plug to the mains, the version of the regulator and factory
settings parameters
L.1
–
L.7
,
H.0
–
H.9
and
d.0
–
d.6
and their values appear on the screen after
2 seconds. 30 seconds after connecting the device to the mains, the entire system starts up
and starts heating the water in the buffer tank for DHW. The device starts operating and
operates until the set breaking temperature is reached. The breaking temperature is factory
set to
52 °C
. After shut-down the operation is interrupted until the water cools for 5 °C, i.e. to
47 °C. When the water in the buffer tank for DHW reaches this temperature, the device turns
on again. The user can freely raise the set breaking temperature but no more than 55 °C
(restriction of the regulator) or freely lower it. Overheating the water to 65 °C is factory restricted
to this value and cannot be readjusted.
NOTE
The device operates with intake air from approx. +5 °C to approx. 35 °C (depending
on relative moisture).