7.2 The program and parameters
The controller provides setting the operation in five different programmes described below and
enables setting three different desired heating temperatures.
The “Antifreeze” programme P.0 enables the display of set temperature of the programme.
Programmes “Normal” P.1, “Res. Source”, P.0 and “Automatic” P.5 enable settings of one
value of desired temperature.
The programme “Photovoltaic” P.6 enables a different setting of the desired temperature value
set with the parameter L.6 and is activated with an active external signal.
The programme “External signal” P.7 will be activated with an active external signal and thus
enable the setting of a third desired heating temperature.
Programmes
Mark of the
programme
Name
P.0
Programme “Antifreeze”
P.1
Programme “Normal”
P.3
Programme “Res. source”
P.5
Programme “Automatic”
P.6
Programme “Photovoltaic - PV”
P.7
Programme “External signal”
NOTE
Pressing the key
P
for the first time checks the currently selected operating
programme. Pressing the key
P
in the time frame of 8 seconds switches between
different programmes.
Parameters
Parameter
mark
Description
Scope
Default
L.0
Evaporator temperature in
°C (only display)
–15–95 °C
L.1
Min. operation temp. in °C –15-30 °C
[0]
L.2
Time
interval
of
overheating in days
- -; 1–99 days
[14]
L.3
Display of active outputs
(only display)
0–5
0 – no output is active
4 – EG
5 – HP + EH
L.4
Standby
1-10 °C
[5]
L.5
Automatic quick water
heating
- -; 1–50 °C
[- -]
L.6
Raising the temperature
at PV
1-20 °C
[5]
L.7
Standby at PV signal
1-10 °C
[3]
NOTE
Water overheating in programme
P.5
,
P.6 or P.7
is performed with the currently
active heat generator.