2
PROFIBUS PA
10
VFC 200
www.krohne.com
06/2019 - 4005059401 - AD VFC200 PB-PA R01 en
Manufacturer specific Ident. number (4541 hex)
This setting provides complete functionality of the PROFIBUS PA device. All Function Blocks are
available for cyclic data transfer. Device specific diagnosis information is transferred in addition
to the Profile diagnosis.
•
AI: Analog Input
•
AO: Analog Output
•
FB: Function Block
There are separate settings to select the units for local display and PROFIBUS. Modifications of
the units of the display will have no effect on the data transferred via PROFIBUS.
A master class 2 tool is required to modify the units for PROFIBUS transfer.
GSD File required:
GSD file KR014541.GSD
KR014541.GSD
KR014541.GSD
KR014541.GSD is required in this mode. This GSD file provides complete functionality of
the PROFIBUS PA device. All function blocks are available for cyclic data transfer.
Slot
Description
Function Block types
Default unit
1
Volume Flow
AI-FB
m
3
/h
2
Vortex Freq.
AI-FB
Hz
3
Volume
Totaliser-FB
m
3
4
Mass
Totaliser-FB
kg
5
Density
AI-FB
kg/m
3
6
Temperature 1
AI-FB
K
7
Pressure
AI-FB
Bar
8
Ext. Temp.
AO-FB
K
Table 2-6: Cyclic layout for manufacturer specific Ident. Number
Totaliser-FB
AI-FB
AO-FB
Empty Module
TOT (Ext.): Total
TOT (Ext.): Se Mod
Total
TOT (Ext.): Se Total
TOT (Id.F.): Total
TOT (Id.F.): Total
TOT (Id.F.): M Total
TOT (Id.F.):
Total
TOT (Id.F.): SetTot
TOT (Id.F.): ModeTot
TOT (Id.F.): ModeTot
Empty Module
AI: Out
AI (nc): Out
AI (Ext.): Out
AI (ld.F.): Out
Empty Module
Aux. Input: SP
Aux. Input (Ext.): SP
Aux. Input (ld.F.): SP
Table 2-7: Valid GSD Modules
INFORMATION!
If another GSD file is used in the PROFIBUS master system the cyclic data transfer cannot be
established in this setting.