or signal lost indication (F)
3.4.3 PULS/UNIT - PULSRATE
(pulse/unit or pulse rate depends on selection in 3.4.2)
PULSE/UNIT
:
Program number of pul-
ses per unit of volume:
Pulse per volumetric unit:
Range (maximum):
PulS/m3
9.9990 E 8
PulS/Liter
9.9990 E 5
PulS/US G
3.7850 E 6
PULSRATE
:
Program pulses per unit
of time at full scale flow:
Pulse rate unit:
Range:
Min.
Max.
PulSe/Sec
2.7778 E-3
1.0000 E 4
PulSe/min
1.6667 E-1
6.0000 E 5
PulSe/hr
1.0000 E 1
3.6000 E 7
3.4.4 T - CONST. F
:
Time constant of fre-
quency output
(see 3.3.5 T- CONST.I)
Program one of the two options for the time constant of the
frequency output:
T<F> = T<I>
:
Equal to the time con-
stant of the current out-
put (see 3.3.5).
T<F> = 40 msec
65