Fig.D.9: Positive flow (F)
3.4.2 PULSOUTP.
:
Frequency output mode
Select one of the two frequency output modes using the
key and press to store:
PULSE/UNIT
:
Pulses per unit of volu-
me.
PULSRATE
:
Pulses per unit of time
at full scale flow.
Example of PULSE/UNIT
:
Pulse value
:
10 pulses per m3 (set
via Fct.3.4.3)
After 60 m3 have passed
:
Output: 600 pulses
since start.
Example PULSRATE
:
Full scale setting
:
1000 liters per second
(set via Start Up Menu)
Pulse rate full scale flow
:
1000 pulses per second
(set via Fct. 3.4.3)
At 600 liters per second
:
Output: 600 Hz signal.
64
ALTOSONIC
Programming mode
UFM 600 T