Messages in AMS, PDM and FC 475 device diagnostic Actions
Standard
NE 107
Signal
[12]
Error message
Error correction
Extended device status
Extended device status
Extended device status
Extended device status -Extended status information about the device status are supported with command 0, 9 and 48.
One byte in the response of the three enumerated commands, give more detailed information, which are listed in the
table below
Transmitter
M
Maintenance required
Check device specific diagnostic for more information
about sensors and transmitter.
Transmitter
M
Device variable alert
Check device specific diagnostic for more information
about sensors and transmitter.
Transmitter
F
Critical power failure
NA
Transmitter
N
Failure
One or more Device Variables are invalid due to a
malfunction in the field device or its peripherals.
Make a self test to find out more. Check even device
specific diagnostic. If the error remains replace the device.
Transmitter
N
Out of specification
Inndication of deviations from the permissible ambient or
process conditions have been detected that may
compromise measurement or control accuracy.
Transmitter
N
Function check
One or more Device Variables are temporarily invalid (e.g.
frozen) due to ongoing work on the device