7
TECHNICAL DATA
44
OPTITEMP TT 53 C/R
www.krohne.com
06/2018 - 4006523501 - MA OPTITEMP TT 53 R01 en
HART
HART
HART
HART
®
HART
®
protocol
HART
®
7
HART
®
physical layer
FSK 1200
Permissible load
(Supply voltage-8)/0.022
NAMUR compliance
Output limits and failure currents acc. to NAMUR NE 43
Adjustable filtering level
0.17 to 90 s, (default 1.4 s) (3-wire RTD)
Monitoring
Sensor break and short circuit monitoring, selectable, upscale
≥
21.0 mA or
downscale
≤
3.6 mA action, individually configurable.
Configuration
Configuration
Configuration
Configuration
ConSoft
The PC configuration software, ConSoft, is a versatile and user-friendly tool
for transmitter configuration.
Consoft is compatible with Windows XP/Vista/7/8/8.1/10
ConSoft is part of the complete configuration kit, which also contains a USB
Interface and necessary cables.
Full functionality of the transmitter is achieved with ConSoft program
version 3.3.0 or later and the firmware in the USB Interface must have a
version number 1.2.07 or later.
KROHNE Connect
The app KROHNE Connect for portable devices(smartphones) is a versatile
and user-friendly tool for wireless configuration through Bluetooth
®
or
NFC
®
technology.
Communication via Bluetooth
®
requires the Bluetooth
®
interface -
TT-CON BT, which can be ordered from the manufacturer.
Alternatives
Hand held communicator, e.g. FC 475 (Emerson)
Management systems, e.g. AMS (Emerson) and PDM (Siemens)
EDD enabled systems
DTM/FDT enabled systems
Approvals and certifications
CE
The device fulfils the statutory requirements of the EC directives.
The manufacturer certifies that these requirements have been met by
applying the CE marking.
Ex approvals
Ex approvals
Ex approvals
Ex approvals
Standard version
Without
Intrinsically safe (IS) version
See Ex approvals
Ex approvals
Ex approvals
Ex approvals in separate table below.
Other standards and approvals
Other standards and approvals
Other standards and approvals
Other standards and approvals
Electromagnetic compatibility
Directive: 2014/30/EU
Harmonized standards: EN 61326-1 and EN 61326-2-3
NAMUR NE 21
EN 61326-1 and -2-3: Criteria A
NE 21: <0,5% of span
RoHS
Directive: 2011/65/EU
Harmonized standard: EN 50581:2012
Vibration resistance
Acc. to IEC 60068-2-6, test Fc, 10...2000 Hz, 10 g
Radio Equipment Directive
This product contains NFC communication and conform to the requirements
of the Radio Equipment Directive (RED) 2014/53/EU