OPTITEMP TT 53 C/R

www.krohne.com

06/2018 - 4006523501 - MA OPTITEMP TT 53 R01 en

5.6  Configuration with ConSoft

The ConSoft is a PC based graphical user interface for configuration of the transmitters. The PC 
configuration software ConSoft is used for configuration, display and documentation. The 
current software versions of ConSoft and the USB interface are available for downloading on our 
website.

To upgrade your USB interface software to the latest version, use the following flow chart.

CAUTION!

When the USB interface (configuration modem) is connected to the transmitter then the HART

®

 

communication is disconnected, even if ConSoft is not running.

1

Is the USB interface version 1.2.00 or higher?

1a

No

1b

Yes

2

No possibility of updating for hardware version below 1.2.00. Replace the USB 
interface with newer version.

3

Is a ConSoft version 1.2.0.0 or higher installed on your PC?

3a

No

3b

Yes

4

Download the current ConSoft version from our website and install it on your 
PC.

5

Download the current software file [USB_x.y.zz.hex] for the USB interface from 
our website to your PC either on your desktop or in a folder made for this 
purpose.

6

1. Start ConSoft
2. Connect the USB interface to the PC. Note that no other device should be 
connected during updating of the USB interface.
3. Click on Options/Update USB Interface/Load file (type the path for the 
software file downloaded on your desktop or in a separate folder).
4. Wait until "File OK" message is on the screen.
5. Click on "Start update". A message "Programming!" and a green status 
indicator show up on the screen. The update will take about one minute.
6. Wait until "Ready USB Interface" message is displayed on the screen. Close 
the update window. The USB interface is now ready for use.

Summary of Contents for OPTITEMP TT 53 C

Page 1: ...TITEMP TT 53 C R OPTITEMP TT 53 C R OPTITEMP TT 53 C R OPTITEMP TT 53 C R Handbook Handbook Handbook Handbook KROHNE 06 2018 4006523501 MA OPTITEMP TT 53 R01 en The documentation is only complete when...

Page 2: ...any part thereof without the prior written authorisation of KROHNE Messtechnik GmbH Subject to change without notice 2 O www krohne com 06 2018 4006523501 MA OPTITEMP TT 53 R01 en Copyright 2018 by KR...

Page 3: ...mitter 13 3 2 Rail mounting kit for in head transmitters 14 3 3 Rail mount transmitter 15 4 Electrical connections 16 4 1 Safety instructions 16 4 2 Electrical connections of in head transmitter 17 4...

Page 4: ...s availability 37 6 3 Availability of services 37 6 4 Returning the device to the manufacturer 37 6 4 1 General information 37 6 4 2 Form for copying to accompany a returned device 38 6 5 Disposal 38...

Page 5: ...ters might cause an explosion that can result in fatal injuries DANGER Responsibility for the correct use of the devices with special regard to suitability intended use and the field of application li...

Page 6: ...ctive 93 68 EC RoHS Directive 2011 65 EU harmonized standard EN 50581 2012 Radio Equipment Directive RED 2014 53 EU The manufacturer certifies successful testing of the product by applying the CE mark...

Page 7: ...n over the Internet e g when communicating by e mail may involve gaps in security It is not possible to protect such data completely against access by third parties We hereby expressly prohibit the us...

Page 8: ...ion To prevent any injury to the user or damage to the device it is essential that you read the information in this document and observe applicable national standards safety requirements and accident...

Page 9: ...warnings must be observed without fail Even partial disregard of this warning can lead to serious health problems and even death There is also the risk of seriously damaging the device or parts of th...

Page 10: ...ilable for downloading on our website You can find configuration instructions in the ConSoft reference manual ConSoft is compatible with Windows XP Vista 7 8 8 1 10 TT 53 C In head transmitter The in...

Page 11: ...or round nameplate 1 Product name 2 CE marking EC conformity 3 Ex relevant electrical data 4 Part number serial number yyww year and week of manufacturing and batch number 5 Printable field sensor con...

Page 12: ...e marking 4006067302 Nyyww xxxxxx PO ZZZZZZZZZ www krohne com OPTITEMP TT 53 R KIWA 17ATEX0056 X IECEx KIWA 17 0030X 0539 II 1 G Ex ia IIC T6 T4 Ga Max ambient 85 C Uo 6 5 V Io 11 7 mA Po 19 1 mW Co 2...

Page 13: ...lly safe version must be supplied by an intrinsically safe power supply unit or Zener barrier placed outside of the potentially explosive zone The Ex transmitter must be installed in a housing with th...

Page 14: ...he transmitter until it is attached to the clip INFORMATION The rail mounting kit allows to install the in head transmitter on a rail according to EN 60715 DIN 50022 The kit does not belong to the sta...

Page 15: ...22 1 Fix the upper part of the transmitter onto the rail 2 Press the lower part of the transmitter against the rail 3 To remove the transmitter bend the locking device using a small screwdriver Carefu...

Page 16: ...ation in potentially explosive areas must be observed In potentially explosive areas only Ex approved HART modems must be used In order to ensure reliable HART communication with this transmitter the...

Page 17: ...wire connection Pt100 Pt100 Pt100 Pt100 Pt1000 Ni100 Ni120 Cu10 Pt1000 Ni100 Ni120 Cu10 Pt1000 Ni100 Ni120 Cu10 Pt1000 Ni100 Ni120 Cu10 3 wire connection 3 wire connection 3 wire connection 3 wire con...

Page 18: ...ure 4 1 Connection diagram 1 Voltage supply 8 5 36 VDC terminals 6 7 2 HART Modem 3 Input 4 Output 5 Thermocouple 6 Pt100 3 wire connection INFORMATION The HART modem is connected parallel to the outp...

Page 19: ...N The HART modem is connected parallel to the output load or parallel to the output of the transmitter DANGER The transmitter may be operated in areas with potentially explosive atmospheres if the vol...

Page 20: ...00 Pt1000 Ni100 Ni120 Cu10 Pt1000 Ni100 Ni120 Cu10 Pt1000 Ni100 Ni120 Cu10 Pt1000 Ni100 Ni120 Cu10 3 wire connection 3 wire connection 3 wire connection 3 wire connection Pt100 Pt100 Pt100 Pt100 Pt100...

Page 21: ...tage supply 8 5 36 VDC and output 4 20 mA INFORMATION The HART modem is connected parallel to the output load or parallel to the output of the transmitter The load must be at least 250 for HART to wor...

Page 22: ...ice For multiple connections Multidrop mode the following formula shall be used L 65 x 106 R x C x Cn x 5000 10000 C with L cable length m or ft R load resistance incl the resistance of any Zener barr...

Page 23: ...oes not need any power or other external connection just to be close to the smartphone The APP makes it possible to read write save and share settings directly in the field The logging function give t...

Page 24: ...e INFORMATION In order to ensure reliable HART communication with this transmitter the loop resistance must be at least 250 If the USB interface configuration modem is connected to the transmitter the...

Page 25: ...transmitter or other HART devices The current outputs of the devices must be passive 1 Primary master 2 HART modem 3 HART signal 4 Other HART devices or this transmitter refer also to 7 5 Terminal 7 6...

Page 26: ...pecifications DANGER Only an Ex approved HART modem located in safe area may be connected to a transmitter placed in potentially explosive area Menu Parameter Factory settings Device Root menu Sensor...

Page 27: ...on below 1 2 00 Replace the USB interface with newer version 3 Is a ConSoft version 1 2 0 0 or higher installed on your PC 3a No 3b Yes 4 Download the current ConSoft version from our website and inst...

Page 28: ...face TT CON Ex to the transmitter Figure 5 1 Connection during configuration of in head transmitter a PC configuration kit b PC software ConSoft 1 Input intrinsically safe 2 RLoad intrinsically safe 3...

Page 29: ...safe 4 Communication with USB interface and a PC software ConSoft 5 Connection to USB interface and a PC software ConSoft is not permitted if Ex version of TT 53 R TT 53 R Ex is placed in the classifi...

Page 30: ...an be configured via the PC software as AMS Asset Management System and Simatic PDM Asset Management Solutions Device Manager AMS Asset Management Solutions Device Manager AMS Asset Management Solutio...

Page 31: ...ffline Root Menu for offline configuration 5 9 Configuration with PACTware PACTware is a DTM FDT enabled PC software which can be downloaded from krohne com To be able to configure the transmitters vi...

Page 32: ...l revisions the Field Device Status had to be set to 0 if a communication error is reported Messages in AMS PDM and FC 475 device diagnostic Actions Standard NE 107 Signal 12 Error message Error corre...

Page 33: ...c diagnostic for more information about sensors and transmitter Transmitter M Device variable alert Check device specific diagnostic for more information about sensors and transmitter Transmitter F Cr...

Page 34: ...valid Check Linearization table settings If error remains replace device Transmitter F Loop voltage too low N A Transmitter F Dac out of range Digital to Analog Converter out of max range Power cycle...

Page 35: ...ter M Linearization table Overrange N A Transmitter S High Alarm Check the sensor and sensor connection If error remains replace the sensor Transmitter S Low Alarm Check the sensor and sensor connecti...

Page 36: ...ion software 5 14 System or sensor error correction System error correction System error correction System error correction System error correction To perform a System error correction a dry block cel...

Page 37: ...d installation kit 70ADA00017 Ex Configuration kit including Ex approved modem Not a HART modem software Consoft and cables for USB connection 4001107902 HART PC modem USB 70MEM00003 TT CON BT interfa...

Page 38: ...e when it is returned Date Signature Stamp LEGAL NOTICE Disposal must be carried out in accordance with legislation applicable in your country Separate collection of WEEE Waste Electrical and Electron...

Page 39: ...tance of metals increases according to a mathematical function as the temperature rises This effect is taken advantage of by resistance temperature sensors to measure temperature The Pt100 temperature...

Page 40: ...red If however the measuring point and the cold junction are at the same temperature no thermoelectric voltage is generated The degree of thermoelectric voltage also known as electromotive force EMF d...

Page 41: ...s Features HART compliance The transmitters are fully compliant with the HART 7 protocol HART 7 offers the possibility to receive diagnostic information such as sensor errors or sensor conditions tran...

Page 42: ...tegory In head transmitter Housing IP65 Terminals IP00 Rail mount transmitter Housing IP20 Terminals IP20 Installation conditions Mounting In head transmitter DIN B head or larger DIN rail with adapte...

Page 43: ...es Input thermocouples Input thermocouples Input thermocouples T C type B Pt30Rh Pt6Rh IEC 60584 400 1800 C 752 3272 F T C type C W5Re W26Re ASTM E 988 0 2315 C 32 4199 F T C type D W3Re W25Re ASTM E...

Page 44: ...ser friendly tool for wireless configuration through Bluetooth or NFC technology Communication via Bluetooth requires the Bluetooth interface TT CON BT which can be ordered from the manufacturer Alter...

Page 45: ...fe TT 53 C Ex intrinsically safe TT 53 C Ex intrinsically safe ATEX KIWA 17ATEX0054 X II 1G Ex ia IIC T6 T4 Ga IECEx IECEx KIWA 17 0028X Ex ia IIC T6 T4 Ga TT 53 R Ex intrinsically safe TT 53 R Ex int...

Page 46: ...ions In head transmitter In head transmitter In head transmitter In head transmitter Rail mount transmitter Rail mount transmitter Rail mount transmitter Rail mount transmitter Dimensions mm inch a 33...

Page 47: ...ead transmitter Intrinsically safe transmitter Rail mount transmitter Rail mount transmitter Rail mount transmitter Rail mount transmitter Intrinsically safe transmitter Temperature class Ambient temp...

Page 48: ...maximum permissible output load permissible RLoad U 8 5 0 022 INFORMATION Shaded areas shows the working area of the HART communication Standard transmitter Figure 7 3 Output load diagram X Power sup...

Page 49: ...mount transmitter Rail mount transmitter Rail mount transmitter Rail mount transmitter Intrinsically safe transmitter TT 53 R Ex Output terminals 6 7 Input terminals 1 2 3 4 Ui Vmax 30 VDC Uo U0C 6 5...

Page 50: ...01 of span per C RTD Cu10 50 260 83 1 5 C or 0 2 of span 0 02 of span per C T C type B 400 1800 700 1 0 C or 0 2 of span 2 0 01 of span per C T C type C 0 2315 200 1 0 C or 0 2 of span 2 0 01 of span...

Page 51: ...F or 0 1 of span 2 0 006 of span per F T C type C 32 4199 360 1 8 F or 0 1 of span 2 0 006 of span per F T C type D 32 4199 360 1 8 F or 0 1 of span 2 0 006 of span per F T C type E 454 1832 90 0 9 F...

Page 52: ...degree of protection of at least IP20 North America 1 The configuration of the associated apparatus or intrincically safe equipment or simple apparatus shall be approved 2 Safety barriers must be ins...

Page 53: ...06 01 4 If the cable parameters are unknown the following values shall be used Capacitance 200 pF m 60pF feet Inductance 0 66 H m 0 20 H feet 5 If the safety barrier requires an earth conection then t...

Page 54: ...9 NOTES 54 OPTITEMP TT 53 C R www krohne com 06 2018 4006523501 MA OPTITEMP TT 53 R01 en...

Page 55: ...NOTES 9 55 OPTITEMP TT 53 C R www krohne com 06 2018 4006523501 MA OPTITEMP TT 53 R01 en...

Page 56: ...cess Analysis Services Head Office KROHNE Messtechnik GmbH Ludwig Krohne Str 5 47058 Duisburg Germany Tel 49 203 301 0 Fax 49 203 301 10389 info krohne com KROHNE 06 2018 4006523501 MA OPTITEMP TT 53...

Reviews: